TP-6517 1/11
18
Section 2 Operation
5. Move the generator set master switch to OFF/
RESET.
6. Reconnect the generator set to the load using the
line circuit breaker or ATS.
7. Move the generator set master switch to the AUTO
position for startup by remote transfer switch or
remote start/stop switch.
Note:
The controller’s LED display remains off
until an engine start command is received.
Code Fault
Description
Check
HE
High engine
temperature
shutdown
Shutdown occurs if the engine coolant temperature exceeds
the maximum temperature for more than 5 seconds. This
protective becomes active after the engine reaches the crank
disconnect speed.
Check for blocked air inlets and
exhaust outlets.
LO
P
Low oil
pressure
shutdown
Shutdown occurs if a low oil pressure condition exists for more
than 5 seconds. This protective becomes active 30 seconds
after the engine has reached crank disconnect speed
(30 second inhibit).
Note:
The low oil pressure shutdown does not protect against
low oil level. Check the oil level at the engine.
Check for leaks in the lubrication
system.
Check the oil level and add oil if
the level is low.
OC
Overcrank
shutdown
Shutdown occurs after 3 unsuccessful starting attempts. The
crank cycle is set for three starting attempts of 15 seconds
cranking and 15 seconds rest.
Check the fuel supply, spark plug,
and battery.
Check for loose connections.
Contact an authorized
distributor/dealer for service if
problem continues.
Locked rotor
The generator set also shuts down on OC if no engine rotation
is sensed during cranking. Shuts down 3 seconds after the
fault is detected.
OF
Overfrequency
shutdown
Shutdown occurs when the governed frequency exceeds 110%
of the system’s frequency setpoint for more than 5 seconds.
This protective becomes active 10 seconds after engine start
(10 second inhibit).
Contact an authorized
distributor/dealer for service if
problem continues.
OS
Overspeed
shutdown
Shutdown occurs if the engine speed exceeds 110% of the
normal running speed for more than 0.3 seconds.
Contact an authorized
distributor/dealer for service if
problem continues.
UF
Underfrequency
shutdown
Shutdown occurs if the governed frequency falls below 54 Hz
for more than 5 seconds.
Shutdown also occurs if the governed frequency falls below
56.5 Hz for more than 60 seconds.
This protective becomes active 10 seconds after engine start.
(10 second inhibit).
Reduce the load and restart the
generator set.
Contact an authorized
distributor/dealer for service if
problem continues.
UU
Undervoltage
shutdown
Shutdown occurs if the voltage falls below 80% of the nominal
system voltage for more than 10 seconds.
Reduce the load and restart the
generator set.
Contact an authorized
distributor/dealer for service if
problem continues.
LB
Low battery
voltage warning
Fault code is displayed if the engine starting battery voltage
falls below 11 VDC for more than 30 seconds when the engine
is not running. Not operative during the engine crank cycle,
this fault condition does not inhibit engine starting.
The fault condition clears when the battery voltage returns to an
acceptable level.
Check the battery rating and
condition.
Check the battery charger
operation.
Charge or replace the battery.
Figure 2-3
DC-RET Fault Codes
Summary of Contents for 12RESL
Page 14: ...TP 6517 1 11 14 Section 1 Features Notes...
Page 20: ...TP 6517 1 11 20 Section 2 Operation Notes...
Page 30: ...TP 6517 1 11 30 Section 3 Scheduled Maintenance 12 kW Models Notes...
Page 42: ...TP 6517 1 11 42 Section 5 Troubleshooting Notes...
Page 45: ...Notes...
Page 46: ...Notes...
Page 47: ......