Section 10 Voltage Reconnection and Wiring Diagrams
10.1.2 100--120/200--240-Volt
Configurations
This configuration does not use a jumper lead. If the unit
was originally wired for straight 100--120 volt, 3 wire,
remove
the
jumper
lead
(see
Figure 10-1
and
Figure 10-2 for location).
Select a circuit breaker
manufactured with a 2-pole circuit breaker. Two 1-pole
circuit breakers do not conform to NEC requirements
when supplying a 200--240-volt load. This is true even if
they are mechanically attached together. Since leads
L1 and L2 are different phases,
never
connect them
together.
60 Hz
50 Hz
L0--L1
100--120 Volt
100--120 Volt
L0--L2
100--120 Volt
100--120 Volt
L1--L2
200--240 Volt
200--240 Volt
4
3
2
1
Stator Leads
LO (Neutral)
Line
Side
Factory
2-Pole
Circuit
Breaker
Ground
Load
Side
100--120/200--240 Volt, 3 Wire
LO
GRD
L2
L1
Figure 10-3
100--120/200--240 Volt, 3 Wire
10.1.3 200--240-Volt Configurations
This configuration does not use a jumper lead. If the unit
was originally wired for straight 100--200 volt, 3 wire,
remove
the
jumper
lead
(see
Figure 10-1
and
Figure 10-2 for location).
60 Hz
50 Hz
L0--L1
not used
200--240 Volt
4
3
2
1
Stator Leads
LO
GRD
L1
LO (Neutral)
Line
Side
1-Pole
Circuit
Breaker
Ground
Load
Side
200--220--240 Volt, 2 Wire
Tape to insulate
from ground
Figure 10-4
200--240 Volt, 2 Wire
Summary of Contents for 10EOZ
Page 2: ......
Page 4: ...TP 6053 7 04 Table of Contents Notes ...
Page 10: ...TP 6053 7 04 VI Safety Precautions and Instructions Notes ...
Page 22: ...TP 6053 7 04 10 Section 2 Scheduled Maintenance Notes ...
Page 24: ...TP 6053 7 04 12 Section 3 Intake and Exhaust System Notes ...
Page 30: ...TP 6053 7 04 18 Section 4 Fuel System Notes ...
Page 44: ...TP 6053 7 04 32 Section 6 Controller Troubleshooting Notes ...
Page 62: ...TP 6053 7 04 50 Section 9 Generator Disassembly Reassembly Notes ...
Page 70: ...TP 6053 7 04 58 Section 10 Voltage Reconnection and Wiring Diagrams Notes ...
Page 79: ......