TP-6591 10/13
18 Section 2 Operation
Fault Shutdowns
Code
Description
Sensing
Mechanism
Active
State
Inhibit
Time
Delay
Time
Default
Setting Check
Over crank
(fault)
Overcrank
shutdown occurs
after 3
unsuccessful
starting attempts.
Fail to start
Excessive
crank cycles
0 sec
7 sec on/
15 sec off
3 crank
cycles
Check the fuel supply and battery.
Also check for loose connections.
Contact an authorized
distributor/dealer for service if
problem continues.
Locked rotor
(fault)
Overcrank (locked
rotor) shutdown
ECM data
Excessive
locked rotor
cycles
0 sec
3 sec
3 sec
Contact an authorized
distributor/dealer for service if
problem continues.
Low oil pres
(fault)
Low oil pressure
shutdown occurs if
a low oil pressure
condition exists.
Note:
The low oil
pressure shutdown
does not protect
against low oil
level. Check the
oil level at the
engine.
ECM data
Below setting
30 sec
5 sec
7 psi
Check for leaks in the lubrication
system.
Check the oil level and add oil if the
level is low.
Over speed
(fault)
Overspeed
shutdown occurs
if the engine
speed exceeds
the default setting.
ECM data
Above setting 0 sec
1 sec
70 Hz
Contact an authorized
distributor/dealer for service if
problem continues.
Coolant loss
(fault)
Loss of coolant
shutdown occurs
after a loss of
coolant condition
is detected.
Digital input
Grounded
30 sec
5 sec
N/A
Check for a clogged seawater intake
or sea strainer.
Check for a damaged seawater pump
impeller.
Check for a clogged or dirty seawater
flow switch.
Check for damaged water lines.
Check for proper installation.
Check for inlet restriction exceeding
the seawater pump’s maximum inlet
restriction.
Hi eng temp
(fault)
High engine
temperature
shutdown occurs if
the engine coolant
temperature
exceeds the
default setting.
Note:
The high
engine temp.
shutdown
functions only
when the coolant
level is in the
operating range.
ECM data
Above setting 30 sec
5 sec
230
_
F
Check for a low engine coolant level.
Check seawater pump impeller,
strainers, and seacock.
Aux input
(fault)
Auxiliary fault
input shutdown.
Note:
Input from a
customer-supplied
switch that closes
when the fault is
active.
Digital input
Grounded
3 sec
0.3 sec
N/A
Check the cause of the auxiliary fault.
Summary of Contents for 10EKD-Low CO
Page 4: ...TP 6591 10 13 4 Notes...
Page 8: ...TP 6591 10 13 8 Safety Precautions and Instructions Notes...
Page 12: ...TP 6591 10 13 12 Section 1 Service Views Notes...
Page 48: ...TP 6591 10 13 48 Notes...
Page 49: ...TP 6591 10 13 49 Notes...
Page 50: ...TP 6591 10 13 50 Notes...
Page 51: ...TP 6591 10 13 51 Notes...