TP-6591 10/13
17
Section 2 Operation
2.6.3
Stopping the Generator Set
The following procedures describe the actions required
to stop the generator set.
Local Stopping.
1. Run the generator set at no load for at least
2 minutes to ensure adequate engine cooldown.
2. Press the Start/Stop button to stop the generator
set. The engine stops.
3. Press the Power Button to turn the controller off.
Remote Stopping.
1. Run the generator set at no load for at least
2 minutes to ensure adequate engine cooldown.
2. The generator set stops when the remote start/stop
switch or remote digital gauge contacts close
momentarily.
Consult the instruction sheet supplied with the remote
start/stop switch or remote digital gauge for stopping
instructions.
Note:
ADC II powers down after 48 hours of inactivity. If
the generator has been started, the controller will
power down 48 hours after the generator stops.
2.6.4
Fault Shutdowns and Warnings
The generator set shuts down automatically under the
fault conditions listed in Figure 2-6 and the controller
displays a fault code. The generator set cannot be
restarted until the fault condition is corrected and the
controller is reset. See Section 2.6.5 to reset the
controller after a fault shutdown. The controller resets
automatically after a battery voltage fault condition is
corrected.
Shutdown switches on the generator set automatically
reset when the problem is corrected. The high engine
temperature switch automatically resets when the
generator set cools. However, the fault does not clear
until the controller is reset.
The controller displays warning text but the generator
set does not shut down under the conditions shown in
Figure 2-7.
Summary of Contents for 10EKD-Low CO
Page 4: ...TP 6591 10 13 4 Notes...
Page 8: ...TP 6591 10 13 8 Safety Precautions and Instructions Notes...
Page 12: ...TP 6591 10 13 12 Section 1 Service Views Notes...
Page 48: ...TP 6591 10 13 48 Notes...
Page 49: ...TP 6591 10 13 49 Notes...
Page 50: ...TP 6591 10 13 50 Notes...
Page 51: ...TP 6591 10 13 51 Notes...