MJ400215A1
13
24) RSFD
:
Acquisition of the set flow rate [significand] (digital)
The set flow rate [significand] (digital) that has been set is acquired.
This is used to calculate the set flow rate (digital) together with the flow rate
decimal point position [number of decimal places] and flow rate unit.
Data Command: None
Response: Decimal 4 digits (fixed length 4 bytes)
Range: 0000
-
9999
25) WSFD
:
Setting of the set flow rate [significand] (digital)
Set the set flow rate [significand] (digital).
Set the set flow rate (digital) together with the flow rate decimal point position
[number of decimal places] and flow rate unit.
Data Command: Decimal 4 digits (fixed length 4 bytes)
Range: 0000
-
full scale flow rate [significand]
However, setting less than 2% of the full scale flow rate
[significand] is treated as fully closed.
Response: None
26) RALA
:
Acquisition of the response to alarm occurrence
The response to alarm occurrence is acquired.
Data Command: None
Response: Decimal 1 digit (fixed length 1 byte)
0
:
Valve control continued,
1
:
Valve forced to fully closed
2
:
Valve forced to fully opened
27) WALA
:
Setting of the response to alarm occurrence
Set the response to alarm occurrence.
Data Command: Decimal 1 digit (fixed length 1 byte)
0
:
Valve control continued
1
:
Valve forced to fully closed
2
:
Valve forced to fully opened
Response: None