-13-
8-3 Mechanical stopper
Setting is to be made so as that as shown in [Fig.15], contact output switch will function at 3°~6° before
position limit switch function point, and mechanical stopper will function at 3°~6° after position limit
switch function point.
* On / off positions of the actuator main unit will be determined by output shaft position.
Set position / signal limits and mechanical stopper manually as shown in the figure, while confirming
the positions of full close and full open.
Adjustment Bolt
Locknut
Output Shaft
(Full close position)
Stopper
Full close
0 %
50 %
Full open
100 %
Control angle 90°
Mechanical Stopper
Function Point
Close Position Limit
Switch Function Point
Close Signal Limit
Switch Function Point
[Fig.15]
Mechanical Stopper
Function Point
Open Position Limit
Switch Function Point
Open Signal Limit
Switch Function Point