FINAL TEST
1
.
Ensure that the second output of the TWIN WATER VALVE is closed.
NOTE
Only 1 side of the TWIN WATER VALVE is used. The other one must be closed properly.
2
.
With WATER ON, check that all HOSE CLAMPS and all ADAPTERS are tight.
3
.
Switch on the ML2000 P.
4
.
Connect the DVM to TEST POINTS TP5 (Plus) and to TP2 (Gnd) of the SENSOR
PCB A16. See the drawing on the next page.
5
.
Adjust R5 until the voltage reading is 5 VDC. This is equal to a relative humidity
of 50 % RH.
6
.
If the relative humidity is below 50% the HUMIDIFIER FAN will start. and the WATER
RESERVOIR is filled.
T h i s s i d e o f t h e T W I N W A T E R V A L V E
m u s t b e c l o s e d .
figure 1-13
II 3477-D
HUMIDIFIER ML2000 P
INSTALLATION INSTRUCTIONS