9.5   Rate   

9.5.1 

Rate / Measuring rate 

Parameter "Measuring rate" specifies the time interval within which the input signal is 
recorded, the flow rate is calculated and brought to display. The condition of all other 
outputs which depends on the flow rate (analogue output, switching outputs and status 
output) will be recalculated after the measurement time. 
The "sampling rate" can be increased in steps of 0.5 sec. up to 10 sec. An increase in 
the sampling rate time on one hand causes increase in the filtering time of the input 
signals, but also an increased reaction time in the detection of changes in the flow 
values.   

9.5.2 

Rate / Unit 

The unit displayed for the flow rate measurement can be selected from various 
predefined standard units. The definition of a user-defined unit ("User") is possible, 
here the „User Unit “must be programmed in Liter/min.  
e.g.: 
Unit: user = 100 LPM, if flow = 500 LPM then the flow rate shown on display will be 5 
user. 

9.5.3 

Rate / Start  

The parameter "start point" defines the lower flow rate limit for display and further 
evaluation. If the measured flow rate lies below the measuring range value, the flow 
rate is set to "0", therefore "hidden". At the same time the "underflow" icon will appear 
in the display. 
If the value of the parameter is set to "0", this feature is effectively disabled. 

9.5.4 

Rate / End  

With parameter "End point", the upper measurement limit of the connected sensors / 
transducers is set. 
Depending on the actual flow display, the decimal point for the bigger display adjusts 
itself automatically. 

 

Flow Display 

Decimal points on 

the Display 

0.1 to 9.9999 

10 to 99.999 

100 to 999.99 

1000 to 9999.9 

10000 to 99999 

If the flow rate is displayed on the smaller display, the number of decimal points is 
fixed to 4 and cannot be changed. However the digits before the decimal point change 
themselves automatically from e.g. 0-9999 [Unit] depending upon the actual flow. 

9.5.5 Rate 

Measurement / Over flow value 

The parameter "overflow value" is set in "% of full scale" 
Example: "end point" = 100 [L / m], "overflow value" = 10 [%] 

 

The arrow pointing upwards on the top right side of the display will 
be shown when flow display shows 110 l/m. 

Summary of Contents for ZOE series

Page 1: ...Operating Manual for Flow Totalizer Model ZOE...

Page 2: ...d Menu Structure 18 8 1 Overall 18 8 2 Measuring Mode 18 8 3 Menu Mode 19 9 Instrument Parameters 21 9 1 End of instrument parameterization 21 9 2 Overview of menu functions instrument parameters 22 9...

Page 3: ...e measuring unit should be used only when the machines fulfil the EC machine guidelines 2 1 Notice according to the Battery Law Old batteries do not belong in household waste You can send the batterie...

Page 4: ...culation display and transfer of calculations and flow rates of flow meters with pulse or frequency outputs The instruments display flow rate day counter resettable and total counter in the operator s...

Page 5: ...n x x Supply voltage DC supply x Battery operation x x Sensor supply only with external supply 8 V Electrical outputs only with external supply Pulse output x LCD Display Selectable units x X Decimal...

Page 6: ...r NPT are available for electric connection in case of electronics with plastic housing To use these cable inlets the existing factory protection caps must be broken with a tool e g screwdriver and a...

Page 7: ...3 6V 2200mAh Size AA ext Batt Service 7 2 Overview of Terminals ZOE ZX with Supply option B and 3 Supply option B only battery either 1 x 3 6V or 2 x 1 5V Supply option 3 with battery either 1 x 3 6V...

Page 8: ...option ZOE ZX can also be powered by a battery In battery mode the device function scope is relatively limited Pulse output is not available The backlight of the display is switched off and cannot be...

Page 9: ...Sensor Inputs 7 4 1 Active pulse signal Power Supply External DC Supply Signal input setting ACTIVE SIGNAL Wiring for ZOE ZE with Supply option 3 Wiring for ZOE Z with Supply option B Battery 1 5V Si...

Page 10: ...ZOE Page 10 ZOE K04 0718 7 4 2 Hall Sensor NPN and PNP Sensors Power supply only external DC supply Signal input setting HALL Signal input setting NPN Signal input setting PNP Wiring for ZOE ZE...

Page 11: ...ZOE ZOE K04 0718 Page 11 7 4 3 Reed switch Signal input setting REED Wiring for ZOE ZE with Supply option 3 Wiring for ZOE Z with Supply option B...

Page 12: ...supply External DC supply and battery operation Battery operation reduces battery life Signal input setting COIL Wiring for ZOE ZE with Supply option 3 The connection of the DOT turbine wheel flowmet...

Page 13: ...ZOE ZOE K04 0718 Page 13 7 4 5 Namur Sensor Power supply only external DC supply Signal input setting NAMUR Wiring for ZOE ZE with Supply option 3 Battery 3 6V 2200mAh Size AA...

Page 14: ...ZOE Page 14 ZOE K04 0718 7 4 6 Transducer model UMF2 Power supply only external DC supply Signal input setting NPN Wiring for ZOE ZE with Supply option 3 5 4 Battery 3 6V 2200mAh Size AA...

Page 15: ...hrough a an active control input or b Carried out by a passive N O contact In both cases the function will be activated on switching from HIGH to LOW level falling edge When using an active control si...

Page 16: ...ZOE Page 16 ZOE K04 0718 Wiring for ZOE ZE with Supply option 3 Battery 3 6V 2200mAh Size AA...

Page 17: ...17 7 6 Pulse Output Pulse output is set to push pull output type and provides an active digital signal with HIGH amplitude of about Vs Wiring for ZOE ZE with Supply option 3 Battery 3 6V 2200mAh Size...

Page 18: ...the supply voltage the electronics starts in measurement mode In this mode the input signals are recorded continuously current instantaneous flow and volume counter readings are periodically calculate...

Page 19: ...mode is turned on the input signal detection and pulse output are still active in the background After leaving the menu mode all display parameters are then updated again in measurement mode Note The...

Page 20: ...all menu groups can not be displayed simultaneously on the screen so the list of menu items can then be scrolled up or down To choose the selected item button should be pressed and the device goes in...

Page 21: ...the cursor can be moved again to left by pressing key and the correction can be made If the cursor is on the far right the set value is saved by pressing the button and the display changes to the pare...

Page 22: ...SIGNAL TYPE nPn For NPN sensors List selection default Battery external COIL For induction coils Battery external PnP For PNP sensors Battery external ACt For active pulse signals Battery external nAm...

Page 23: ...S 10 Battery external COUNTER UNIT mL L m3 galUS galUK User Volume units for counter List selection L Battery external RST PART Reset subset counter A Button selection Yes No No Battery external PULSE...

Page 24: ...to detect even lower frequencies Input Timeout parameter can be configured up to 20 s After the completion of Refresh time the signal processing waits for the full input period until the additional wa...

Page 25: ...automatically activated In case of other sensors it is by default inactive and can be activated by the user anytime using Menu 9 4 Scaling The correct scaling of the signal inputs is necessary for ex...

Page 26: ...ions for the base sequence The sensor curve must be monotonically increasing since the frequency values increase continuously with increasing flow Inconsistent base sequence After entering the lineari...

Page 27: ...ameter start point defines the lower flow rate limit for display and further evaluation If the measured flow rate lies below the measuring range value the flow rate is set to 0 therefore hidden At the...

Page 28: ...totalizer counter values on smaller as well as the bigger display with the help of different layouts available under DISPLAY menu However the bigger display is limited to display only 5 digits If the...

Page 29: ...earized Behaviour at OVERFLOW If the measured volumetric flow lies in the OVERFLOW range the pulse output is switched off and a constant HIGH level is switched at the output Generation of the output p...

Page 30: ...th the activation of a user password the access to menu for the user can be locked by a master user 9 8 1 User service Change password The default administrator user password is set to 00000 the user...

Page 31: ...1 1000 Hz High low threshold 0 6 VDC Minimum input voltage for coil input 30 mVpp Measuring rate 1 s Units for volume flow ml h l m m3 h gpmUK gpmUS gphUK gphUS User Units for volume counter ml l m3...

Page 32: ...sal mount round plastic for retrofitting DON M 3xM20x1 5 cable entry N 3x NPT cable entry F pulse frequency input B 1 battery for operation 0 without 0 without Y special please specify in clear text Z...

Page 33: ...ZOE ZOE K04 0718 Page 33 12 Dimensions mm ZOE ZXK ZOE ZXM...

Page 34: ...2013 Electrical equipment for measurement control and laboratory use EMC requirements Part 1 General requirements Also the following EC guidelines are fulfilled 2014 30 EU EMC Directive 2011 65 EU RoH...

Reviews: