DVZ
DVZ K04/0810
page 15
If the window point (duo-point) is less than or equal to the switching
point, an error report (Er4) will be indicated on the display and its
value is deleted and its function is invalid (in the case that the
window point and switching point out of adjustment).
The value is set in the same way as the switching point.
The window point is needed for process, in which monitoring of a certain
temperature range is necessary.
Example:
Switching point: 100 L/min; window point: 150 L/min;
hysteresis: -1 L/min
The electronic switches when 100 l/min is exceeded. If the switching value
remains between 99 L/min (100-1) and 151 L/min (150+1), the contact will also
remain in active switching condition (LED on). If it exceeds 151 l/min or is below
99 l/min the electronic switches back.
Switching behaviour
The following diagram clarifies the switching behaviour of the electronic switch.
The contact closes (contact type: no) when it drops below the switching point or
the window point. It only opens again if the window point plus hysteresis is
exceeded or if it drops below the switching point minus hysteresis. An
LED
indicates the switching condition of the switching point.
Time / t
Display
bar (°C)
Hysteresis
LED on
Time / t
Display
bar (°C)
Switchpoint
Hysteresis
LED on
Hysteresis
Window point
LED on
Summary of Contents for DVZ series
Page 1: ...Operating Instructions for Compact Vortex Flow Meter Model DVZ ...
Page 23: ...DVZ DVZ K04 0810 page 23 DVZ sensor with fixed connection measuring range from 40 L min AF o ...
Page 28: ...DVZ page 28 DVZ K04 0810 13 2 Dimensions Electronics DVZ S30x DVZ F3x0 DVZ L3x3 DVZ L443 ...
Page 29: ...DVZ DVZ K04 0810 page 29 DVZ C3xx ...