KÖBER SRL VADURI
BRANCH
7
7.2.2 Minimum necessary distances/ free spaces for mounting
8. Installation
Danger!
Danger of death by poisoning and explosion because of breeches in the gas
pipes and connections in case of incorrect installation! Installation and
commissioning can be done only by a company authorized and agreed by
KÖBER SRL-Vaduri Branch! This company will assume responsibility for the
correct installation and commissioning.
Fig.
1.3
100
100
400
250
Both for the mounting/ installation of the central
heating BOILERS and for later maintenance
operations you will need the following minimum
distances (fig. 1.3), respectively minimum free
spaces for mounting:
– distance to the lateral: 100 mm
– distance to the bottom part: 250 mm
– distance to the upper part: 400 mm
– distance to the front part: 400 mm
8.1Conditions for the installation of the central heating BOILER
8.1.1 Installation indication
The central heating BOILER will be subject to corrosion from the moment it is filled with water!
To receive warranty during the entire warranty period it is essential to take into
consideration the following directions in order not to increase the corrosion!
- The burning gas must have the sulphur content within the limits of the applicable European
standard: it is accepted for a short period of time to have a maximum of 150 mg/m3, but the
yearly average must be of 30 mg/m3.
- The burning air must not contain chlorine, ammonia, alkaline agents, halogenated
hydrocarbs, freon, plaster particles, lints, dirt or dust;
- Installation of the central heating BOILER in the proximity of a swimming pool, washing
machine or cleaner can result in the contamination of the burning air with these
compounds.
- Water pH must be within the following limits: 7,5<pH<9,5
It is recommended to check the water and thermal agent pH frequently and if the value does
not fall within the limits provided by the manufacturer, it will be treated again.
- Water asperity must be within the limits 5°F <TH <15°F (5°F (French degrees), equivalent to
50 mg CaCO or an equivalent quantity of other Ca and Mg salts).
3
Caution!
Danger of damaging the equipment by
incorrect setting!
The equipment can be mounted only on
a flat, fixed surface.
Note!
Minimum necessary distances/ free spaces for mounting are valid also for
mounting with/ within pieces of furniture.
EN
USER MANUAL C33GC24