1
6
5 The ECOTRONIC control system
5.1 General information
The ECOTRONIC facility control system is a decentralised
microprocessor system (CAN-BUS) developed by KÖB
with various modules that are connected by a data trans-
mission line.
Its function
The ECOTRONIC records all the data relevant to operation
and controls the supply of and demand for heat.
Thus the boiler plant is continuously monitored during all
the operating phases and kept within an optimum range in
terms of emissions.
Factory settings (pre-settings)
All the parameters in the ECOTRONIC, such as set point
values and switching times, are pre-set and can be called
back up at any time. The figures for the factory settings
are given in brackets for the various parameters.
5.1.1 Replacing the battery
There is a battery built in beneath the removable lid on the
control module (type: Panasonic Lithium BR2330). It is
for buffering the time, date and settings.
-
The battery needs replacing every five years!
-
Do not disconnect the mains voltage while changing
the battery (do not turn off master switch)!
5.2 The functions of the keys
F1 (PYROT Wood)
Switch WOOD operation on and off
F2 (PYROT Oil)
Switch OIL OPERATION on and off
F3 (PYROT Parameters)
Setting parameters, set point values, the date and time
F4 (PYROT Loader System)
Setting of cycle switchover switching, advance-flow and
post-flow times
F5 (Group 1)
Setting parameters and set point values
(heat distribution, Group 1)
F6 (Group 2)
Setting parameters and set point values
(heat distribution, Group 2)
F7 (Group 3)
Setting parameters and set point values
(heat distribution, Group 3)
F8 (Group 4)
Setting parameters and set point values
(heat distribution, Group 4)
<
<
<
<
Go one page to the left in menu masks
>
>
>
>
Go one page to the right in menu masks
∧
∧
∧
∧
Go one line up
(Only possible when the scroll up symbol
is dis-
played.)
∨
∨
∨
∨
Go one line down
(Only possible when the scroll down symbol
is
displayed.)
+
Change numeric values and set point values
-
Change numeric values and set point values
OK
Adopt (acknowledge) settings and/or changes
The following applies to the F3, F4, F5, F6, F7 & F8 but-
tons:
-
Pressing once will take you to the respective menu. As
feedback, the relevant LED will blink.
-
If a set point value is changed and not confirmed with
"OK", then it will not be adopted.
-
Pressing the function button again will bring back the
standard display.
-
When no button is pressed for a period of sixty sec-
onds, the standard display automatically reappears.
BE SURE TO NOTE:
Depending on the design and setting, some menus and
texts do not appear.
Summary of Contents for PYROT KPT 1250