KNX Jung 230011SU Operating Instructions Manual Download Page 7

Switch actuator, 1-gang

Connection mode

Screw terminals

Switching voltage

AC 250 V ~

Switching current

16 A

Fluorescent lamps

16 AX

Switch-on current 200 μs

max. 800 A

Switch-on current 20 ms

max. 165 A

Connected load
Ohmic load

3000 W

Capacitive load

max. 16 A (140 μF)

Motors

1380 VA

Incandescent lamps

2300 W

HV halogen lamps

2300 W

HV-LED lamps

max. 400 W

LV halogen lamps with electronic transformers

1500 W

LV halogen lamps with inductive transformer

1200 VA

Compact fluorescent lamps uncompensated

1000 W

Compact fluorescent lamps parallel com-
pensated

1160 W (140 μF)

Reduction of switching current
per 5 °C in excess of 35 °C

-10%

when installed in wooden or dry construction walls

-15%

when installed in multiple combinations

-20%

Clampable conductor cross-section
single stranded

0.5 ... 4 mm²

Finely stranded without conductor sleeve

0.5 ... 4 mm²

Finely stranded with conductor sleeve

0.5 ... 2.5 mm²

Connection torque screw terminals

Max. 0.8 Nm

Inputs
Control cable (preterminated)

YY6x0.6

Input type

Potential-free

Number

3

Total length of extension device cable

max. 10 m

Cable type (preferably)

J-Y(St)Y

Poll voltage, extension inputs

approx. 5 V

6

Accessories

External sensor

FF7.8

Condensation sensor

BTS01

Leakage sensor

LES01

7

Warranty

The warranty is provided in accordance with statutory requirements via the specialist trade.

7 / 8

82404313

25.05.2021

J0082404313

Summary of Contents for Jung 230011SU

Page 1: ...tallation that there is always sufficient insula tion between the mains voltage and the bus A minimum distance of at least 4 mm must be maintained between bus conductors and mains voltage cores Danger...

Page 2: ...ula tion in building automation and can be configured in the ETS project Detailed specialist know ledge is required A device certificate which is attached to the device is required for safe com missio...

Page 3: ...n Disabling functions Debounce time adjustable Logic function characteristics Logic gates Transformer conversion Disabling element Comparator Limit value switch 4 Information for electrically skilled...

Page 4: ...ronic device box with partition Ob serve cable routing and spacing Figure 3 Figure 3 Mounting example in electronic device box with partition wall series push button and NTC temperature sensor 5 Appli...

Page 5: ...er with COM connections of other devices 4 2 Commissioning Commissioning the device NOTICE Undefined relay state at delivery Unexpected control of connected loads During commissioning before switching...

Page 6: ...ice setting physical address 15 15 255 firmware re mains in place The device must then be recommissioned with the ETS During secure operation A master reset deactivates device security The device can...

Page 7: ...of switching current per 5 C in excess of 35 C 10 when installed in wooden or dry construction walls 15 when installed in multiple combinations 20 Clampable conductor cross section single stranded 0...

Page 8: ...itch actuator 1 gang ALBRECHT JUNG GMBH CO KG Volmestra e 1 58579 Schalksm hle GERMANY Telefon 49 2355 806 0 Telefax 49 2355 806 204 kundencenter jung de www jung de 8 8 82404313 25 05 2021 J008240431...

Reviews: