Switch actuator, 1-gang

Figure 5: Connection of load

Observe ambient temperature. Ensure adequate cooling.

Connect the device to KNX with the correct polarity.

Connect load as shown in the connection example (Figure 5).

If required, connect potential-free contacts or dew/leakage sensors to inputs 1...3, or NTC
temperature sensors to input 3 (Figure 2).

Install the device in the appliance box.

In secure operation: The device certificate must be removed from the device and stored
securely.

The COM reference potential must not be connected together with COM connections of
other devices!

4.2 Commissioning

Commissioning the device

NOTICE!

Undefined relay state at delivery.

Unexpected control of connected loads.

During commissioning, before switching on the load, ensure that all relay contacts
are open by applying the KNX bus voltage. Observe commissioning sequence!

Switch on the KNX bus voltage.

Wait about 10 s.

Connect the load circuit.

Delivery state: Operation of the output via switch at input 1 (ON / OFF) possible. Inputs 2
and 3 have no function.

Function of Inputs in the as-delivered state

Input

Switch

Function

1

closed

ON

1

open

OFF

2

---

---

3

---

---

Load physical address and application program

Press the programming button.
The programming LED lights up.

5 / 8

82404313

25.05.2021

J0082404313

Summary of Contents for Jung 230011SU

Page 1: ...tallation that there is always sufficient insula tion between the mains voltage and the bus A minimum distance of at least 4 mm must be maintained between bus conductors and mains voltage cores Danger...

Page 2: ...ula tion in building automation and can be configured in the ETS project Detailed specialist know ledge is required A device certificate which is attached to the device is required for safe com missio...

Page 3: ...n Disabling functions Debounce time adjustable Logic function characteristics Logic gates Transformer conversion Disabling element Comparator Limit value switch 4 Information for electrically skilled...

Page 4: ...ronic device box with partition Ob serve cable routing and spacing Figure 3 Figure 3 Mounting example in electronic device box with partition wall series push button and NTC temperature sensor 5 Appli...

Page 5: ...er with COM connections of other devices 4 2 Commissioning Commissioning the device NOTICE Undefined relay state at delivery Unexpected control of connected loads During commissioning before switching...

Page 6: ...ice setting physical address 15 15 255 firmware re mains in place The device must then be recommissioned with the ETS During secure operation A master reset deactivates device security The device can...

Page 7: ...of switching current per 5 C in excess of 35 C 10 when installed in wooden or dry construction walls 15 when installed in multiple combinations 20 Clampable conductor cross section single stranded 0...

Page 8: ...itch actuator 1 gang ALBRECHT JUNG GMBH CO KG Volmestra e 1 58579 Schalksm hle GERMANY Telefon 49 2355 806 0 Telefax 49 2355 806 204 kundencenter jung de www jung de 8 8 82404313 25 05 2021 J008240431...

Reviews: