Function | Parameters for media coupler configuration
RF/TP media coupler/repeater | Order no. 5110 00 | 51103300
Page 33 of 42
Configuration via
TP and RF
only TP
only RF
By using the ETS, the device can be programmed and commissioned either via the
TP side (e.g. with a suitable KNX TP USB or IP data interface) or, as an alternative,
via the RF side (e.g. with a KNX RF USB data interface). As needed, it is also pos-
sible using this parameter to prevent programming access to the device depending
on the medium and so prevent changes to the configuration. This allows unwanted
programming attempts (e.g. for unauthorised manipulation) to be suppressed to a
great extent.
Locking or forwarding group telegrams, physically addressed telegrams and
broadcast telegrams (routing) are not affected by the configuration lock. With
the safe-state mode, the configuration lock can be temporarily cancelled in
coupler operation (see chapter "Safe-state mode"
TP and RF
The device can be programmed and read out for diagnostic purposes from the TP or
RF side with no limitation.
only TP
The device can only be programmed and read out via the TP side. Physically ad-
dressed connections reaching the device via the RF side are not responded to. Nor
does the device respond to RF broadcast telegrams.
only RF
The device can only be programmed and read out via the RF side. Physically ad-
dressed connections reaching the device via the TP side are not responded to. Nor
does the device respond to TP broadcast telegrams.
Selection
Telegrams TP -> RF