Function | Configuration lock

RF/TP media coupler/repeater | Order no. 5110 00 | 51103300

Page 29 of 42

Setting up the configuration lock

The parameter "Configuration via" determines whether the configuration lock is active
and to which media it applies.

Set the parameter to "TP and RF".

The media coupler can be programmed and read out for diagnostic purposes
from the TP or RF side with no limitation.

Set the parameter to "only TP".

The device can only be programmed and read out via the TP side. Physically
addressed connections reaching the device via the RF side are not responded
to. Nor does the device respond to RF broadcast telegrams.

Set the parameter to "only RF".

The device can only be programmed and read out via the RF side. Physically
addressed connections reaching the device via the TP side are not responded
to. Nor does the device respond to TP broadcast telegrams.

Summary of Contents for GIRA 5110 00

Page 1: ...Product documentation Issue 14 11 2022 51103300 RF TP media coupler repeater Order no 5110 00 ...

Page 2: ...Update capability 5 1 6 Technical data 6 1 7 Accessories 6 2 Safety instructions 7 3 Mounting and electrical connection 8 4 Commissioning 10 5 Application programs 14 6 Scope of functions 15 7 Notes on software 16 8 Function 17 8 1 Function as media coupler 17 8 2 Function as repeater 23 8 3 LED display 27 8 4 Configuration lock 28 8 5 Parameters for media coupler configuration 30 9 Safe state mod...

Page 3: ...The exact function of the device is determined by the selec ted parameterization and by the physical address Optionally the device can additionally or alternatively work as a repeater A repeater repeats the radio telegrams received in its RF line by retransmitting them immedi ately This allows an extension of the range of a KNX RF installation meaning that it is possible to position RF devices as ...

Page 4: ...ce generations Devices marked I00 No KNX Data Secure compatibility Secure commissioning of other devices via media coupler is not possible with this device version Devices with marking I01 The device is KNX Data Secure compatible with ETS5 7 3 or higher Secure commissioning of other devices via media coupler is pos sible without restrictions from this device version onwards KNX Data Secure offers ...

Page 5: ...51103300 Page 5 of 42 1 5 Update capability The device can be updated Firmware updates e g from device version I00 to I04 can be performed in existing installations with the ETS and a special update applica tion program It is recommended to update media couplers individually and sequentially ...

Page 6: ...ata according to EN 300220 2 KNX TP media coupler segment coupler operation KNX medium TP256 Commissioning mode S mode Rated voltage KNX DC 21 32 V SELV Current consumption KNX 3 9 5 1 mA Repeater operation Rated voltage DC 24 V SELV Degree of protection IP20 Protection class III Ambient temperature 20 45 C Storage temperature 25 55 C Transport temperature 25 70 C Relative humidity 10 100 no moist...

Page 7: ...y skilled persons Serious injuries fire or property damage possible Please read and follow manual fully The radio communication takes place via a non exclusively available transmission path and is therefore not suitable for safety related applications such as emergency stop and emergency call This manual is an integral part of the product and must remain with the end cus tomer ...

Page 8: ...ble For this use a KNX device connection terminal Ensure correct polarity If the media coupler is used as a line coupler the KNX bus cable must be the main line of a TP area If the media coupler is used as a backbone coupler the KNX bus cable must be the TP area line Backbone of the KNX installa tion If the media coupler is used as a segment coupler the KNX bus cable must be the first segment of t...

Page 9: ...edia coupler may heat up to an impermissible temperature In the case of a device with the marking I04 or higher the Repeater Prog mode of the device must be activated before the physical address is pro grammed In the case of connection to a TP bus cable direct ETS program access to the device via the TP side during repeater operation is no longer possible after commissioning Consequently the repea...

Page 10: ...o ject Device has been connected and the power is switched on Project design and commissioning with ETS5 or a more recent version Project design and commissioning as segment coupler with ETS from version 6 0 5 onwards Programming mode is deactivated after the physical address has been suc cessfully programmed or is generally deactivated by a device test power fail ure ETS programming process of th...

Page 11: ...he TP side only to a limited extent e g with the aid of suitable USB or IP data interfaces insofar as the device is connected to the TP line of the associated media coupler Programming access to the device via the RF side is always possible with no limitation e g with a KNX RF USB data interface or via a media coupler After commissioning a repeater can no longer be reached directly via the TP side...

Page 12: ... used TP RF or alternatively a KNX RF USB data interface Where necessary the TP line of the media coupler can be used for voltage supply to the repeater see chapter Mounting and electrical connection Page 8 When programming the repeater via RF For the programming of the physical address and the domain address to be carried out and completed correctly the domain address of the RF line must match th...

Page 13: ...F USB data interface Where necessary the TP line of the media coupler can be used for voltage supply to the repeater see chapter Mounting and electrical connection Page 8 When programming the repeater via RF For the programming of the physical address and the domain address to be carried out and completed correctly the domain address of the RF line must match the domain address of the RF communica...

Page 14: ...version 2920 Summarized description Use as media coupler in the function of area or line coupler depending on the physical address and configuration Use as KNX RF repeater possible Name Media coupler repeater 902211 Version 1 1 for ETS version 6 0 5 onwards from mask version 2920 Summarized description Use as media coupler in the function of area or line coupler depending on the physical address a...

Page 15: ...f group telegrams TP RF RF TP parameterizable Forwarding of physically addressed telegrams TP RF RF TP paramet erizable Forwarding of broadcast telegrams TP RF RF TP parameterizable Telegram repetitions in case of transmission errors for group broadcast and physically addressed telegrams can be set on the TP side Telegram confirmation for group and physically addressed telegrams can be separately ...

Page 16: ...ical address x y 1 255 no media coupler function note that after the physical address has been programmed the repeater can no longer be reached directly via the TP side As a result further programming operations using the ETS e g programming the application program can no longer be executed on the TP side without the media coupler Direct access to the device via the TP side is only possible again ...

Page 17: ...a coupler as backbone coupler The media coupler has a physical address in the form x 0 0 x TP area address e g 1 0 0 If a media coupler is used as a backbone coupler then a total of up to 4 081 RF devices including media couplers can be integrated into the appropriate area The RF devices must then divide themselves up on the backbone line itself and on up to 15 additional subordinate RF lines see ...

Page 18: ...oupler TP PSU Voltage supply TP Media coupler as line coupler The media coupler has a physical address in the form x y 0 x TP area address y TP line address e g 1 1 0 A KNX RF line can contain up to 256 devices including media coupler see figure 3 The media coupler is connected to the main TP line of an area Addi tional TP lines can be set up using additional TP line couplers There may only ever b...

Page 19: ...ent coupler is connected to the first TP segment of the line There may only ever be one segment coupler in an RF segment With ETS version 6 0 5 or higher the device can be used as a segment coupler with the application program Media coupler repeater 902211 It is not possible to create manual filter table entries in the ETS for RF seg ments This means that no additional group addresses can be added...

Page 20: ...ded into two different lines or areas or segments each with their own domain addresses These different areas or lines must also contain their own media couplers for the devices to be able to com municate with one another irrespective of the line The logical connection between two or more KNX RF environments is thus always made via media couplers and higher level TP or IP lines see figure 5 KNX RF ...

Page 21: ...can be used in various lines and areas of a KNX topology The ETS permits such a configuration However media couplers in a shared KNX system can influence each other unfavourably In particular during the commissioning of various bus devices using the ETS ra dio telegrams may be superimposed meaning that radio communication is poor or even impossible Suitable precautions can be taken to avoid such a...

Page 22: ...counter When a transmitter sends a new telegram for the first time it is given the repeat value 6 As soon as a repeater receives this telegram and forwards it the value is reduced by 1 For each additional repetition process via another re peater in the same RF domain the repeat value is again reduced by 1 Once the value is 0 the telegram is no longer repeated With this process an RF telegram can b...

Page 23: ...ich corresponds to a normal participant address of the RF line e g x y 1 or x y 200 x area address y line address and the parameter Physical ad dress is also set accordingly Function as media segment coupler with repeater The device has a physical address in the form x y 0 and works as a coupler see chapter Function as media coupler Page 17 In addition the repeater function can be released with th...

Page 24: ...e must be configured to x y 1 255 RF repeater The operation of one or more repeaters is recommended when the range of the RF domain should be deliberately extended in one or more directions e g in trans property communication or when a part of a building e g ceilings walls metal constructions which weakens the signal need to be overcome Repeaters can be positioned around the media coupler in a sta...

Page 25: ...onger be reached dir ectly via the TP side because the TP transceiver of the device is switched off This feature is necessary because from a topological standpoint a repeater without media coupler function is exclusively assigned to the RF line and no longer to a TP line As a result further programming operations using the ETS can no longer be executed on the TP side without the media coupler Dire...

Page 26: ...a radio telegram is actually transmitted and thereby repeated This random time is of different length for each transmission operation Consequently radio collisions in combination with listen before talk are largely sup pressed to accommodate the possibility that there are several repeaters in one RF domain which so to speak want to transmit at the same time The principle of this collision avoidanc...

Page 27: ...can recognize whether a telegram has already been received and processed or not despite of its identical user data content This internal saving also permits repeaters to recognize whether they themselves have already forwarded the received telegram and therefore do not need to do so again The domain address of an RF telegram and the LFN can be displayed in ETS group or bus monitors under Medium In...

Page 28: ... this in turn overrides the yellow status function fourth display priority 8 4 Configuration lock Function of the configuration lock By using the ETS the device can be programmed and commissioned either via the TP side e g with a suitable KNX TP USB or IP data interface or as an alternative via the RF side e g with a KNX RF USB data interface As needed it is also pos sible to prevent programming a...

Page 29: ...iagnostic purposes from the TP or RF side with no limitation Set the parameter to only TP The device can only be programmed and read out via the TP side Physically addressed connections reaching the device via the RF side are not responded to Nor does the device respond to RF broadcast telegrams Set the parameter to only RF The device can only be programmed and read out via the RF side Physically ...

Page 30: ...as media coupler Depending on the allocated physical address the media coupler operates as either an area or a line coupler The device operates as a line coupler when it has a physical address in the form x y 0 x TP area ad dress y RF line address e g 1 1 0 Then the media coupler is connected to the main TP line of an area The device operates as a backbone coupler when it has a physical address in...

Page 31: ... RF line x y 1 255 RF repeater The device operates exclusively as a repeater without media coupler function A re peater repeats the radio telegrams received in its RF line by retransmitting them im mediately This allows an extension of the range of a KNX RF installation meaning that it is possible to position RF devices as required in a building even in the case of difficult transmission and recep...

Page 32: ...gram broadcast tele gram or physically addressed telegram is received on the TP side flashes on telegram reception at RF own domain The status LED only lights up yellow briefly when a group telegram broadcast tele gram or physically addressed telegram with the domain name of the associated RF domain is received on the RF side flashes on telegram reception at RF all domains The status LED only ligh...

Page 33: ...Locking or forwarding group telegrams physically addressed telegrams and broadcast telegrams routing are not affected by the configuration lock With the safe state mode the configuration lock can be temporarily cancelled in coupler operation see chapter Safe state mode Page 38 TP and RF The device can be programmed and read out for diagnostic purposes from the TP or RF side with no limitation only...

Page 34: ...stem commissioning During normal operation of a KNX system after com missioning it is always recommended to activate the filter function of the group telegrams in both communication directions This is realised by the parameter setting filter default setting block All group telegrams will be blocked No group telegram can pass the coupler from TP to RF filter In accordance with the filter table gene...

Page 35: ...rams are blocked Telegrams RF TP Group telegrams transmit unfiltered block filter This parameter determines whether group telegrams are forwarded from the lower level RF side to the higher level TP side routing RF TP transmit unfiltered All group telegrams will be transmitted The filter table will be disregarded This set ting influences the behaviour of the red status LED As soon as this parameter...

Page 36: ...from RF to TP This means no TP or IP devices can be pro grammed via the RF side device domain filter depending on target coupler address Only physically addressed telegrams with a target address which does not match the coupler area or line address are forwarded Physically addressed telegrams with a target address matching the coupler area or line address are blocked Repetitions in case of TP tran...

Page 37: ...tted At this point it is possible to define when the device confirms the group telegrams received on the higher level TP line always The device always confirms on the higher order TP line every group telegram re ceived only if transmitted The device confirms on the higher level TP line only those group telegrams forwar ded on the lower level RF line physically addressed telegrams always only if tr...

Page 38: ...lowly If the device is working exclusively as a repeater physical address x y 1 255 it is only possible to program the application program and read out device information via the RF side Thus the configuration lock is always act ive on the TP side In this case the lock cannot even be released in safe state mode Activating the safe state mode Disconnect the device connection terminal Hold down the ...

Page 39: ...51103300 Page 39 of 42 Reconnect the device connection terminals or switch the voltage supply back on Safe state mode is deactivated A programming process of the application program via the ETS does not end the safe state mode because there is no automatic restart ...

Page 40: ...e of devices with marking I04 or higher the yellow status LED indicates repeater prog mode Reset delivery state master reset The device can be reset to delivery state at any time even without using the ETS A reset to delivery state is useful when for example the device was mis takenly commissioned with the incorrect physical address x y 1 255 so the repeater is active In pure repeater operation th...

Page 41: ...state RF TP media coupler repeater Order no 5110 00 51103300 Page 41 of 42 The device resets to delivery state Release the programming button The status LED lights red yellow briefly The device is in delivery state ...

Page 42: ...0 51103300 Page 42 of 42 Gira Giersiepen GmbH Co KG Elektro Installations Systeme Industriegebiet Mermbach Dahlienstraße 42477 Radevormwald Postfach 12 20 42461 Radevormwald Deutschland Tel 49 0 21 95 602 0 Fax 49 0 21 95 602 191 www gira de info gira de ...

Reviews: