background image

 

3  

Hardware Features

Control Signal

  Proportional 

0 to 10 VDC or 2 to 10 VDC, switch 

selectable

  Two-position 

See Supply Voltage

Supply Voltage

 

24 VAC (+20%/–15%), 

Class 2 only, or 22–35 VDC

Supply Frequency

 

50/60 Hz for VAC operation

Supply Power

 

3 VA normal operation (all), 19 VA 

peak initializing (fail-safe models)

Initialization Time

 

Up to 30 seconds before fail safe 

(MEP-4652Q/4672Q) is sufficient

-

ly charged, but the actuator will 

respond normally to control signal 

commands during the charge time

Bridge Time

 

Less than 1 second delay for fail-

safe to activate upon loss of power

Feedback Output

 

0/1 to 5 VDC or 0/2 to 10 VDC 

(switch selectable, standard on all 

models)

SPECIFICATIONS

Auxiliary Switches

  2 SPDT 

1 adjustable 0 to 90° and 1 fixed at 

10° from full CW direction (MEP-

4622Q/4672Q only)

  Rating 

6 A resistive load (3 A motor load) 

@ 250 VAC

Fail-Safe Control

 

Switch selectable, CW/OFF/CCW

Fail-Safe Type 

(Electronic) capacitor driven

Angular Rotation

 

0 to 95°, fully adjustable with me-

chanical stop

Position Indication

 

Visual indicator, 0° to 95°

Running Time

 

90° in 3 seconds (powered or op-

tional fail-safe)

Torque 

54 in-lbs. (6 N•m)

Noise Level

 

< 60 dBA max. at 1 meter

NOTE: 

When the 

0

–10 VDC input is selected, selectable 

feedback options are 

0

–5 or 

0

–10 VDC. When the 

2

–10 VDC input is selected, feedback options are 

1

–5 or 

2

–10 VDC.

Non-Rotation Bracket

(HMO-4002)

Gear Disengagement 

Lever

Mounting Surface

Proportional 

Control

Contact Position with

#2 Switch set for CW:

Open = CCW Rotation

Closed = CW Rotation

Contact Position with

#2 Switch set for CCW:

Open = CW Rotation

Closed = CCW Rotation

Power Supply

24 VAC/VDC

Feedback Out

0/1–5 or 0/2–10

2-Postion 

Control

Summary of Contents for MEP-46 Q Series

Page 1: ...tor life MEP 4622Q and MEP 4672Q models also have two built in SPDT auxiliary switches for remote position indication or an auxiliary equipment interface One switch is fully adjustable 0 to 90 and the other is fixed at 10 from full CW direction A three foot cable is included with the switches All actuators mount directly to 1 4 to 5 8 inch 6 to 16 mm round shafts or 1 4 to 7 16 inch 6 to 11 mm squ...

Page 2: ...s Yes Cables HMO 4001 One switch is fully adjustable 0 to 90 and the other is fixed at 10 from full CW direction Connections are made on either fixed terminals that accept 12 26 AWG wiring or on models with auxiliary switches prewired 3 foot 18 AWG cables Models with cables have the larger HMO 4001 T non rotation bracket DIMENSIONS Dimensions are in inches mm 6 000 152 4 1 625 41 3 2 812 71 4 1 56...

Page 3: ... 90 and 1 fixed at 10 from full CW direction MEP 4622Q 4672Q only Rating 6 A resistive load 3 A motor load 250 VAC Fail Safe Control Switch selectable CW OFF CCW Fail Safe Type Electronic capacitor driven Angular Rotation 0 to 95 fully adjustable with me chanical stop Position Indication Visual indicator 0 to 95 Running Time 90 in 3 seconds powered or op tional fail safe Torque 54 in lbs 6 N m Noi...

Page 4: ...O 4001 or HMO 4002 non rota tion bracket included Dimensions 6 000 x 2 812 x 3 406 inches 152 4 x 71 4 x 86 5 mm see Dimensions on page 2 Weight 1 5 lb 0 68 kg Enclosure UL94 5VA flame retardant polymer NEMA 2 and IP54 to guarantee IP54 install an HMO 4521 liq uid tight cord grip Servicing Maintenance free Environmental Limits Operating 22 to 131 F 30 to 55 C Shipping 40 to 176 F 40 to 80 C Humidi...