3
Hardware Features
Control Signal
Proportional
0 to 10 VDC or 2 to 10 VDC, switch
selectable
Two-position
See Supply Voltage
Supply Voltage
24 VAC (+20%/–15%),
Class 2 only, or 22–35 VDC
Supply Frequency
50/60 Hz for VAC operation
Supply Power
3 VA normal operation (all), 19 VA
peak initializing (fail-safe models)
Initialization Time
Up to 30 seconds before fail safe
(MEP-4652Q/4672Q) is sufficient
-
ly charged, but the actuator will
respond normally to control signal
commands during the charge time
Bridge Time
Less than 1 second delay for fail-
safe to activate upon loss of power
Feedback Output
0/1 to 5 VDC or 0/2 to 10 VDC
(switch selectable, standard on all
models)
SPECIFICATIONS
Auxiliary Switches
2 SPDT
1 adjustable 0 to 90° and 1 fixed at
10° from full CW direction (MEP-
4622Q/4672Q only)
Rating
6 A resistive load (3 A motor load)
@ 250 VAC
Fail-Safe Control
Switch selectable, CW/OFF/CCW
Fail-Safe Type
(Electronic) capacitor driven
Angular Rotation
0 to 95°, fully adjustable with me-
chanical stop
Position Indication
Visual indicator, 0° to 95°
Running Time
90° in 3 seconds (powered or op-
tional fail-safe)
Torque
54 in-lbs. (6 N•m)
Noise Level
< 60 dBA max. at 1 meter
NOTE:
When the
0
–10 VDC input is selected, selectable
feedback options are
0
–5 or
0
–10 VDC. When the
2
–10 VDC input is selected, feedback options are
1
–5 or
2
–10 VDC.
Non-Rotation Bracket
(HMO-4002)
Gear Disengagement
Lever
Mounting Surface
Proportional
Control
Contact Position with
#2 Switch set for CW:
Open = CCW Rotation
Closed = CW Rotation
Contact Position with
#2 Switch set for CCW:
Open = CW Rotation
Closed = CCW Rotation
Power Supply
24 VAC/VDC
Feedback Out
0/1–5 or 0/2–10
2-Postion
Control