Caution
DO NOT
connect active 24 VAC circuits to the output block unless the associ-
ated jumper is removed first. Doing so will result in damage to the output and
prevent it from working.
If the associated output will be an analog output, leave the jumper in place.
5. Connect output devices to the module.
6. Connect required power to the input module.
Illustration 4 gives an example of a typical output module configuration.
Using Separate Banks
The outputs are grouped into three banks that share a common switched-termi-
nal. This connection is marked as “SC” on the output block. If you connect a
circuit to this connector it then becomes common to all outputs in that bank.
Configuration
Configuration settings may be required for the inputs or the RS-485 connection.
If you must activate or deactivate pull-ups on the inputs or set the end-of-line
termination for the RS-485 connection, refer to Illustration 1 to locate the input
switches and Illustration 6 for the End-of-Line switches.
Remove jumper
before installing
board
OR
Remove jumper
prior to connecting
active 24 VAC circuits
to the associated
output terminals
Selection Switch
LED
Illustration 4. Override Board Instalaltion
KMD-5831 PLC-28 Direct Digital Controller Installation & Operation Guide
Installation