Timekeeping
The KMD-5551E translator is a BACnet time master device.
Update interval
Daily, weekly, or monthly
Time message type
UTC, local, or both
Setting time
Synchronized to SNTP server, set from computer time, or
manually entered
Niagara compatibility
Compatible with Niagara 3.8 and later. Requires a license and module added to a Niagara
station, typically in a J.A.C.E. controller, on the same BACnet internetwork.
Translation
Translates between one KMD Tier 1 controller, the controllers connected to one KMD Tier
2 network, or both to a BACnet virtual network. Values for KMD input, output, and variable
points are translated between BACnet input, output, and value objects. Translation is
limited to the following properties:
l
Point values and Present values
l
Manual and Out-of-service status
l
Device, controller, and panel names
l
Object and point names, descriptions, and labels
l
Units of measure
Dimensions and mounting
Surface mount or 35 x 7.5 mm DIN rail mounting
5.64 in.
143 mm
1.25 in.
38 mm
6.31 in.
160 mm
6.00 in.
152 mm
Ø .187 in.
4.8 mm
5.50 in.
140 mm
5.95 in.
151 mm
3.16 in.
80 mm
KMD-5551E Translator
Section 1: Introduction
Revision B
7