Value object
Name
Description
BV14
FAN_STATUS
Fan Proof
BV28
LOCAL_OVRD
Local Override Mode
BV36
STPT_HOLD
Hold Temperature Setpoint
Binary value objects (continued)
Value object
Name
Description
MSV1
OCCUPIED_MODE
Occupied Mode
MSV2
SYSTEM_MODE
Control Mode
MSV3
FAN_MODE
Fan Auto-Manual Mode
Table 7–10 Multistate value objects
Schedule object
The AppStat occupancy state is controlled from a standard BACnet schedule
object. The occupancy state is stored in the reference object binary value
object OCC_SCHEDULE. The exception schedule within the schedule object is
represented in the user interface as the holiday schedules.
Object
Name
Description
Object reference
1
SCHED_1
Schedule #1
BV5 (OCC_SCHEDULE)
Table 7–11 Schedule object
Loop objects
The BACnet PID loops are used for valve and fan modulation, staging,
economizer operation, and reheat during dehumidification. The proportional
and integral properties of the cooling and heating loops are available from
the user interface.
Note:
Not all objects are present in every model.
Installation, Operation, and Application Guide for AppStat
Section 7: System integration
Revision G
119
Summary of Contents for BAC-4000 series
Page 6: ...Contents KMC Controls Inc 6 Revision G ...
Page 30: ...Section 2 Installing the AppStat KMC Controls Inc 30 Revision G ...
Page 64: ...Section 4 Commissioning functions KMC Controls Inc 64 Revision G ...
Page 112: ...Section 6 Application drawings KMC Controls Inc 112 Revision G ...
Page 124: ...Section 7 System integration KMC Controls Inc 124 Revision G ...
Page 128: ...power 28 roof top unit 98 rough in 18 Index KMC Controls Inc 128 Revision G ...