background image

BAC-1xx63 Series (6 Relays, 3 Analog Outputs)   

Installation Guide

4-PIPE MODULATING OPTION

(See the FCU—Other Options section on the next page for more options)

VEP-45xxB745/
VEB-43xxxBCK 

Valves with 

MEP-4002 0–10 

VDC Actuators

XEE-6311-050 Transformer

REE-3211 Multi-Voltage Relays

FCU 4-PIPE

MODULATING LAYOUT

CSE-1102 Air Differential 

Pressure Switch

NOTE: EITHER  FAN STATUS (FST) OR 

DISCHARGE AIR TEMP (DAT) CAN 
BE USED ON IN2, BUT NOT BOTH.

STE-1402 Duct 
Sensor, Type III

Fan Coil Unit (FCU)— 

2 or 4 Pipe, Modulating or 2 Position

Input Terminals

FCU Input Connections

BACnet Objects

       IN4

(AI4)

       IN3

Supply Water Temp. (W-TMP)*

AI3

     GND

Ground

 

       IN2

Optional FST or DAT**

AI2

   *Input for Supply Water Temp is typically a 10K,Type III thermistor. 

    Ensure pull-up resistor switch positions are set properly—see 

    Illustration 3 on page 2.

 **Fan Status (FST) or Discharge Air Temperature (DAT) is an optional, 

    selectable input. Ensure pull-up resistor switch positions are set 

    properly (10K position) for the relay, switch, or Type III thermistor.

Output Terminals 

(BAC-1xxx63C)

FCU Output Connections

BACnet 

Objects

2-Pipe

4-Pipe

      Analog 9

(AO9)

  GND

Ground 

(for analog output terminals 7–9)

      Analog 8

Heat Valve, 

Proportional (HTV)

AO8 

      Analog 7

Valve, 

Proportional (VLV)

Cool Valve, 

Proportional (CLV)

AO7

      Relay 6

(BO6)

  SC 4–6

24 VAC (for relay terminals 4–6)

      Relay 5

Heat Valve, 

2-Position (HTV)

BO5

      Relay 4

Valve, 

2-Position (VLV)

Cool Valve, 

2-Position (CLV)

BO4

      Relay 3

Fan 3

BO3

  SC 1–3

24 VAC (for relay terminals 1–3)

 

      Relay 2

Fan 2

BO2

      Relay 1

Fan 1

BO1

 *If optional Outside Air Damper is used, must also have MAT/OAT inputs.

NOTE:

Humidity 

and occupan-

cy sensor 

options are 

dependent 

on FlexStat 

model.

 

APPLICATION

DEGREES SCALE: °F

APP:

OPT: 4–PIPE
ADDITIONAL SETUP

FAN COIL

 

ADDITIONAL SETUP

FAN

HUMIDITY
SENSORS
VALVE

NOTE:  To see Humidity options in 

the Additional Setup menu, 

select the 4-Pipe option.

NOTE: 

Do not use 

REE-3211s 

with analog 

outputs! 

See Output 

Connections 

on page 3.

Summary of Contents for BAC-1xx63 Series

Page 1: ...t windows air vents and air circulation obstructions e g curtains furniture See the Application Guide for more information Additionally for a model with an occupancy sen sor option be sure to install it where it will have unobstructed view of the most typical traffic area see the Application Guide for more information If replacing an existing thermostat label wires as needed for reference when rem...

Page 2: ...six conductor and outputs e g 12 conduc tor is recommended Grounds for all the inputs can be combined on one wire CAUTION To avoid damage from ground loops and other communication issues in networked FlexStats correct phasing on MS TP network and power connections on ALL the networked controllers is critically important MS TP Wiring Connect the A terminals in parallel with all other A terminals on...

Page 3: ...plication Guide Output Connections Connect the device under control between the desired output terminal and the related SC Switched Com mon for relays or GND Ground for analog outputs terminal See Illustration 4 For the bank of three relays there is one Switched relay Common connec tion in place of the GND terminal used with analog outputs See Illustration 5 Relay 3 or 6 SC 1 3 or 4 6 Relay 2 or 5...

Page 4: ...ower Connection The FlexStat requires an external 24 volt AC power source Use a KMC Controls Class 2 transformer to supply power Connect the transformer s neutral lead to the 24 VAC Common C terminal and the AC phase lead to the 24 VAC Phase R terminal See Illustration 4 Power is applied to the FlexStat when the transformer is plugged in KMC Controls recommends powering only one con troller thermo...

Page 5: ...lso have MAT OAT inputs typically 10K Type III thermistors Ensure pull up resistor switch positions are set properly see Illustration 3 on page 2 Fan Status FST or Discharge Air Temperature DAT is an optional selectable input Ensure pull up resistor switch positions are set properly 10K position for the relay switch or Type III thermistor Output Terminals AHU Output Connections Modulating BACnet O...

Page 6: ...inals 1 3 Relay 2 O B Reversing Valve see O B Note in schematic BO2 Relay 1 G Fan BO1 If optional Outside Air Damper is used must also have MAT OAT inputs Input Terminals HPU Input Connections BACnet Objects IN4 Opt Outside Air Temp OAT AI4 IN3 Opt Mixed Air Temp MAT AI3 GND Ground IN2 Optional FST or DAT AI2 When using optional Outside Air Damper must also have MAT OAT inputs typically 10K Type I...

Page 7: ...AT inputs typically 10K Type III thermistors Ensure pull up resistor switch positions are set properly see Illustration 3 on page 2 Fan Status FST or Discharge Air Temperature DAT is an optional selectable input Ensure pull up resistor switch positions are set properly 10K position for the relay switch or Type III thermistor Output Terminals Typical Terminal Codes RTU Output Connections 1 or 2 H a...

Page 8: ...DAT is an optional selectable input Ensure pull up resistor switch positions are set properly 10K position for the relay switch or Type III thermistor Output Terminals BAC 1xxx63C FCU Output Connections BACnet Objects 2 Pipe 4 Pipe Analog 9 AO9 GND Ground for analog output terminals 7 9 Analog 8 Heat Valve Proportional HTV AO8 Analog 7 Valve Proportional VLV Cool Valve Proportional CLV AO7 Relay 6...

Page 9: ... 6311 050 Transformer STE 1454 Temp Sensor 2 PIPE 2 POSITION FCU OPTION XEE 6311 050 Transformer VEP 1xxx0186 VEZ 4xxxxMBx Valve with 24 VAC Actuator BRN VEPSeries or RED VEZ Series BLU VEPSeries or BLK VEZ Series STE 1454 Temp Sensor NOTE See the FCU Overview section on the previous page for the 4 Pipe Modulating option and the general schematic Additional Resources The latest support files are a...

Reviews: