BAC-1xx63 Series (6 Relays, 3 Analog Outputs)
5
Installation Guide
STE-1416 Duct Averaging Temp. Sensor
CSE-1102 Air Differential
Pressure Switch
MEP-5372/7252/7552/7852 Fail-Safe Actuators
XEE-6311-075/6311-100 Transformer
STE-1451 Outside Air Temp. Sensor
VEP-45xxB895/VEB-43xxxBDL Valves with MEP-5372 Fail-Safe Actuators
REE-3211 Multi-Voltage Relay
XEE-6311-075 Transformer
NOTE: EITHER FAN STATUS (FST) OR
DISCHARGE AIR TEMP (DAT) CAN
BE USED ON IN2, BUT NOT BOTH.
AHU LAYOUT
STE-1402 Duct
Sensor, Type III
Applications
Air Handler Unit (AHU)—
Modulating Heat and Modulating Cool
Input Terminals
AHU Input Connections
BACnet Objects
IN4
Opt. Outside Air Temp. (OAT)*
AI4
IN3
Opt. Mixed Air Temp. (MAT)*
AI3
GND
Ground
IN2
Optional FST or DAT**
AI2
*When using optional Outside Air Damper, must also have MAT/OAT
inputs (typically 10K, Type III thermistors). Ensure pull-up resistor
switch positions are set properly—see Illustration 3 on page 2.
**Fan Status (FST) or Discharge Air Temperature (DAT) is an optional,
selectable input. Ensure pull-up resistor switch positions are set
properly (10K position) for the relay, switch, or Type III thermistor.
Output
Terminals
AHU Output Connections
(Modulating)
BACnet
Objects
Analog 9
Outside Air Damper (OAD/RTD)*
AO9
GND
Ground (for analog output terminals 7–9)
Analog 8
Heating Valve (HTV)
AO8
Analog 7
Cooling Valve (CLV)
AO7
Relay 6
(BO6)
SC 4–6
Relay 5
(BO5)
Relay 4
(BO4)
Relay 3
(BO3)
SC 1–3
24 VAC (for relay terminals 1–3)
Relay 2
(BO2)
Relay 1
Fan
BO1
*If optional Outside Air Damper is used, must also have MAT/OAT inputs.
NOTE: See also the RTU section
for 2-stage options.
NOTE: Connections and menus reflect firmware
version R1.3.0.4 or later.
APPLICATION
DEGREES SCALE: °F
APP:
ADDITIONAL SETUP
AIR HANDLER
ADDITIONAL SETUP
DAMPER
FAN
HUMIDITY
SENSORS
VALVE