STAR 14 PELLET BOILER STOVE
13
EN - Rev. 2.1
Chimney
The chimney is a device crowning the flue, used to ease dispersion of combustion products.
It must satisfy the following requirements:
-
It must have a usable outlet cross-section no less than double that of the flue onto which it is inserted;
-
In must be shaped in such a way as to prevent rainwater or snow from seeping into the flue;
-
It must be built in such a way as to ensure the discharge of combustion by-products even in the event of winds from
every direction and inclination.
The outlet height (where height refers to the top of the flue, regardless of any chimney stacks) must be outside of the so-
called reflux zone, in order to prevent the formation of counter-pressures preventing the free discharge of combustion
by-products into the atmosphere.
It is therefore necessary that the minimum heights - indicated in the following diagrams - are observed:
ELECTRICAL CONNECTION
The electric connection must only be performed by qualified staff, in compliance with all general and local safety
standards.
Check that the power supply voltage and frequency correspond to 220V – 50 Hz.
The appliance's safety is ensured when it is properly connected to an efficient earthing system.
In the electric connection to the mains power supply, include a 6 A – Id 30 mA differential trip-switch with suitable
breaking load. The electric connections, including the earth connection, must be made after shutting off the electrical
system.
When completing the system, bear in mind that the cables must be laid in an unmovable manner and far from parts
subject to high temperatures. During the final wiring of the circuit, only use components with a suitable electrical
protection rating. Do not pass electric cables in the immediate vicinity of the flue gas pipe, unless they are insulated with
suitable materials.
KLOVER srl declines all responsibility for injury to persons and animals or damage to objects due to failure to
connect the appliance to earth or to comply with IEC specifications.