KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 | [email protected] | www.klinger.dk
Ultrasonic Heatmeter
Operation Manual
53
$0040
40065
Energy rate unit – char1,2
String
2
Note 2
$0041
40066
Energy rate unit – char 3,4
$0042
40067
Energy total unit – char 1,2
String
1
$0043
40068
Instrument address –low word
32 bits real
2
$0044
40069
Instrument address –high word
$0045
40070
Serial number – char 1,2
String
4
$0046
40071
Serial number – char 3,4
$0047
40072
Serial number – char 5,6
String
4
$0048
40073
Serial number – char 7,8
$0049
40074
Analog Input AI1 Value- low word
32 bits real
2
Returned
temperature value
with RTD option
$004a
40075
Analog Input AI1 Value- high word
$004b
40076
Analog Input AI2 Value- low word
32 bits real
2
$004c
40077
Analog Input AI2 Value- high word
$004d
40078
4-20mA Value- low word
32 bits real
2
Unit: mA
$004e
40079
4-20mA Value- high word
b)
Single Write Register Address List ( use 0x06 performance code to write )
PDU Address
Register
Description
Read/W
rite
Type
No. registers*
$1003
44100
Flow meter address ( 1 - 255 )
R/W
16 bits int.
1
$1004
44101
Communication Baud Rate 0 =
2400,1 = 4800, 2 = 9600, 3 =
19200, 4 = 38400,5 = 56000
R/W
16 bits int.
1
Notes:
1.
The following flow rate units are available:
0.
"m3"
-
Cubic Meter
1. "l"
-
Liters
2. "ga"
-
Gallons