Ultrasonic Heatmeter
Operation Manual
30
M14
Installation space
This value is calculated by the flow meter
The operator must mount the transducer
according to the transducer spacing displayed
(ensure that the transducer spacing is measured
precisely during installation). The system will
display the data automatically after the pipe
parameter had been entered.
M20
Damping
The damping factor ranges from 1 ~ 999 seconds.1
indicates no damping; 999 indicates the maximum
damping.
The damping function will stabilize the flow display.
Usually a damping factor of 3 to 10 is recommended
in applications.
M21
Low Vel. Cut off
Low Flow Cut off is used to make the system display
as "0" value at lower and smaller flows to avoid any
invalid totalizing. For example, if the cutoff value is
set as 0.03, system will take all the measured flow
velocity values from - 0.03 to + 0.03 as "0".
Generally,
0.03
is
recommended
in
most
applications.