DOCUMENTATION OF AUTOMATIC CONTROL
FOR COMPACT UNITS
DTR.MCKT-HPX.
AUT-009.5.0
PAGE
GDYNIA
MCKT-HPX
2016
30/35
KLIMOR Spółka z ograniczon
ą
odpowiedzialno
ś
ci
ą
, 81-035 Gdynia, ul. B. Krzywoustego 5
Fax: (+48 58) 783-98-88; Tel.: (+48 58) 783-99-99
Service – Fax: (+48 58) 783-98-88; Tel.: (+48 58) 783-99-50/51 Mobile: (+48) 510 098 081
Information provided in this document is subject to change
email:
– Office
– Service
Register
address
Code
Description
Type
40009
---
---
Read only
TZAL_BY
MSB: Bypass damper switch on temperature [°C], {5÷35}
Read only
40010
TWYL_BY
MSB: Bypass damper switch off temperature [°C], {5÷35}
Read only
AppNo
LSB: Active application number (0x0F mask)
Read only
40011
TOchrony
MSB: Protection threshold temperature of heat recovery (0x3F
mask) [°C], {0÷30}
Read only
HeatThOn
LSB: Secondary heater switch on threshold in heating sequence
function [%], {0÷99}
Read only
40012
HeatThOff
MSB: Secondary heater switch off threshold in heating sequence
function [%], {0÷99}
Read only
CoolThOn
LSB: Cooler switch on threshold in cooling sequence function [%],
{0÷99}
Read only
40013
CoolThOff
MSB: Cooler switch off threshold in cooling sequence function [%],
{0÷99}
Read only
TO
LSB: Digital outputs
40014
OUTA
MSB: Analog output OUTA {0-255}
Read only
OUTB
LSB: Analog output OUTB {0-255}
Read only
40015
OUTC
MSB: Analog output OUTC {0-255}
Read only
OUTD
LSB: Analog output OUTD {0-255}
Read only
40016
PWM_OC
MSB: Pulse output {0-255}
Read only
ALCRS1
LSB: Alarm condition register
Read only
40017
UNIBOX3v4x
_SOFT_VER
MSB: Firmware version: UNIBOX3v4x [msb7][msb6][msb5][msb4].
UNIBOX3v4x_SOF
T_VER
ALCRS2
LSB: Alarm status register
[x][x][x][x][AL_STOP_IN_PROGRESS]
[AL_AF_HIGH_PREASSURE]
[AL_AF_LOW_PREASSURE][AL_HEATER_HE]
AL_STOP_IN_PROGRESS – alarm requiring an acknowledgment
or delayed turn-off
AL_AF_HIGH_PREASSURE – Heat pump high pressure alarm
AL_AF_HIGH_PREASSURE – Heat pump low pressure alarm
AL_HEATER_HE – H2 electrical heater alarm
Read only
40018
SET_REG1 MSB:[MODBUS_T1][MODBUS_T2][x][x] [x] [x] [x]
[COM2ctrlSTART_bit]
COM2ctrlSTART_bit – external start after COM2
Selection of master sensor by ModBus
[MODBUS_T1][MODBUS_T2]:
00 – TN2
01 – TN
10 – TW
11 – TP
Change possible from
the
BMS/Readout
level
AIR
SUPPLY_
MANUAL
LSB: Air supply fan RPM setting {0-255}
Change possible from
the
BMS/Readout
level