DOCUMENTATION OF AUTOMATIC CONTROL
FOR COMPACT UNITS
DTR.MCKT-HPX.
AUT-009.5.0
PAGE
GDYNIA
MCKT-HPX
2016
29/35
KLIMOR Spółka z ograniczon
ą
odpowiedzialno
ś
ci
ą
, 81-035 Gdynia, ul. B. Krzywoustego 5
Fax: (+48 58) 783-98-88; Tel.: (+48 58) 783-99-99
Service – Fax: (+48 58) 783-98-88; Tel.: (+48 58) 783-99-50/51 Mobile: (+48) 510 098 081
Information provided in this document is subject to change
email:
klimor@klimor.pl
– Office
serwis@klimor.pl
– Service
Register
address
Code
Description
Type
40007
CRS1
MSB: Condition register 1:
[T1][T2][MODE1][MODE0][DS2present][RUN]
[DS1present][DS0present]
Current operation mode
[MODE1] [MODE0]
00 – MIN mode
01 – MAX mode
10 – ULUB mode
11 – STREFA mode
Master sensor selected at the [T1] [T2] panel
11 – DS3 sensor (Tp)
10 – DS2 sensor (Tw)
01 – DS1 sensor (Tn)
00 – DS5 sensor (Tn2)
RUN – ON/OFF override from the panel
DS0present – presence of the Tz temperature sensor
DS1present – presence of the Tn temperature sensor
DS2present – presence of the Tw temperature sensor
Read only
CRS2
LSB: Condition register 2:
[DS3present][VDI1][VDI2][VDI3][VDI4]
[VDI5][DS5present][DS4present]
VDI1 – operation permit provided by the Calendar
in case of operation in the ZONE mode)
VDI2 – bypass actuator operation
VDI3 – switching on the preliminary electric heater/ground heat
exchanger
VDI4 – anti-frost protection active
VDI5 – alarm with confirmation
(1 – no alarm with confirmation,
(0 – alarm with confirmation is present)
DS3present – presence of the Tp temperature sensor
DS4present – presence of the To temperature sensor
DS5present – presence of the Tn2 temperature sensor
Read only
40008
CRS3
MSB: Condition register3:
[VDI13][VDI12][VDI11][VDI10][VDI9][VDI8][VDI7][VDI6]
VDI6 – operation permit for the H2 heater
VDI7 – operation permit for the H1 preliminary heater
VDI8 – operation permit for the C cooler
VDI9 – not used
VDI10 – cooling sequence lock based on external temperature
VDI11 – heating sequence lock based on external temperature
VDI12 – heater H2 pump control based on external temperature
VDI13 – not used
Read only
EFF
LSB: Heat exchanger efficiency calculated according to the formula
(Tn-Tz)/(Tw-Tz) * 100% [%], {0-99%}
Read only