8
extraction rail
ERGO-KOS-AL
30.01.2019
Connection between the suction duct and the extraction fan
:
The
KPC
connection (of the
KOS-AL
duct) ought to be connected with the fan inlet by means
of conduits and fitting pieces type SPIRO spiral-seam duct. The diameters of these elements
should match the assumed duct connections.
It is recommended:
–
to install a silencer type
T
before the fan inlet
– the silencer length ought to be not less
than 500 mm,
–
to connect the inlet and outlet of the fan with the installations by means with a flexible joint.
Flexible joints do not convey vibrations from the fan to the installation. Depending on the type,
the fan has to be installed on the roof on a fan pedestal or on a roof base, in case of indoor ap-
plication
– on wall brackets.
Selection of a fan:
a/
For applications with an indoor fan we suggest using the fan
WPA-E-N
series of fans of
KLIMAWENT S.A. production.
Fig. No.7
– WPA-E-N – Flow charts