background image

Air Evacuation

3

Preparations and Precautions

Air and foreign matter in the refrigerant circuit 
can cause abnormal rises in pressure, which 
can damage the air conditioner, reduce its 
efficiency, and cause injury. Use a vacuum pump 
and manifold gauge to evacuate the refrigerant 
circuit, removing any non-condensable gas and 
moisture from the system.
Evacuation should be performed upon initial 
installation and when unit is relocated.

BEFORE PERFORMING EVACUATION

  

Check to make sure that both high-
pressure and low-pressure pipes between
the indoor and outdoor units are
connected properly in accordance with the
Refrigerant Piping Connection section of
this manual.

  

Check to make sure all wiring is connected
properly.

Evacuation Instructions

Before using the manifold gauge and vacuum 
pump, read their operation manuals to familiarize 
yourself with how to use them properly.

Manifold Gauge

Compound gauge

-76cmHg

Low pressure valve

High pressure 
valve

Pressure hose / 
Charge hose

Charge hose

Vacuum
pump

Pressure gauge

Low pressure valve

1. Connect the charge hose of the manifold

gauge to service port on the outdoor unit’s
low pressure valve.

2. Connect another charge hose from the

manifold gauge to the vacuum pump.

MC

MC

Fig. 6.1

Air Evacuation

Summary of Contents for ksie series

Page 1: ...OUTDOOR UNIT Installation Manual IMPORTANT NOTE Read this manual carefully before installing or operating your new air conditioning unit Make sure to save this manual for future reference SERIES...

Page 2: ...ort the unit and will not vibrate Noise from the unit will not disturb others Protected from prolonged periods of direct sunlight or rain DO NOT install unit in the following locations Near an obstacl...

Page 3: ...outdoor unit If the drain joint comes with a rubber seal see Fig 4 4 A do the following 1 Fit the rubber seal on the end of the drain joint that will connect to the outdoor unit 2 Insert the drain jo...

Page 4: ...n bolt 5 Hammer expansion bolts into the pre drilled holes 6 Remove the nuts from expansion bolts and place outdoor unit on bolts 7 Put washer on each expansion bolt then replace the nuts 8 Using a wr...

Page 5: ...odes and must be installed by a licensed electrician 2 All electrical connections must be made according to the Electrical Connection Diagram located on the side panels of the indoor and outdoor units...

Page 6: ...the terminal block and place it to the side 4 Match the wire colors labels with the labels on the terminal block and firmly screw the u lug of each wire to its corresponding terminal 5 After checking...

Page 7: ...Conditioner 15 000 25 82ft 10 33ft 15 000 and 24 000 30 98 5ft 20 66ft 24 000 and 36 000 50 164ft 25 82ft 36 000 and 60 000 65 213ft 30 98 5ft Connection Instructions Refrigerant Piping Step 1 Cut pi...

Page 8: ...th PVC tape to prevent foreign materials from entering the pipe 2 Sheath the pipe with insulating material 3 Place flare nuts on both ends of pipe Make sure they are facing in the right direction beca...

Page 9: ...5 1 500 11lb ft 1 600 11 8lb ft 9 52 0 375 2 500 18 4lb ft 2 600 19 18lb ft 12 7 0 5 3 500 25 8lb ft 3 600 26 55lb ft 16 0 63 4 500 33 19lb ft 4 700 34 67lb ft DO NOT USE EXCESSIVE TORQUE Excessive fo...

Page 10: ...Using a spanner grip the body of the valve Do not grip the nut that seals the service valve See Fig 5 10 USE SPANNE R TO GRIP MAIN BOD Y OF VALVE Torque from tightening the flare nut can snap off oth...

Page 11: ...pipes between the indoor and outdoor units are connected properly in accordance with the Refrigerant Piping Connection section of this manual Check to make sure all wiring is connected properly Evacu...

Page 12: ...w pressure by hand You may tighten it further using a torque wrench if needed OPEN VALVE STEMS GENTLY When opening valve stems turn the hexagonal wrench until it hits against the stopper Do not try to...

Page 13: ...nit immediately and call a licensed electrician to find and resolve the cause of the leakage Note This may not be required for some locations in the US Gas Leak Checks There are two different methods...

Page 14: ...r to turn it on 3 Press the MODE button to scroll through the following functions one at a time COOL Select lowest possible temperature HEAT Select highest possible temperature 4 Let each function run...

Page 15: ...rol return unit to normal operating temperature b Using insulation tape wrap the indoor refrigerant pipe connections that you left uncovered during the indoor unit installation process IF AMBIENT TEMP...

Page 16: ...s Dispose of the appliance at designated municipal electronic waste collection facility When buying a new appliance the retailer will take back the old appliance free of charge The manufacturer will t...

Page 17: ...t improvement Consult with the sales agency or manufacturer for details 2190 NW 89 Place Doral FL 33172 USA Tel 305 593 8358 Fax 305 675 2212 www klimaire com sales klimaire com The Klimaire logo is a...

Reviews: