HM700A1000
PLUMBING
Fig. 4. Water supply and drain connection.
IMPORTANT
r
All water supply and drain line connections should be
installed in accordance with local plumbing codes.
r
Drain water is automatically cooled to 140 °F (60 °C)
when HM700 cycles a drain. When the manual drain
switch is used, temperature may be higher. The drain
material (tube and drain) must be rated for 200 °F
(93 °C).
p
Supply water should be between 30 to 100 PSIG. A throttle
valve may be used if necessary.
p
Do not use reverse osmosis or de-ionized water. Supply
water should be between 150-1200 S (microsiemens) for
optimal conductivity.
p
Supply water should be cold, 34 to 68 ºF (1 to 20 ºC).
p
Install water shut off valve before humidifier to facilitate
servicing.
p
The drain line should not end in a sink used frequently by
personnel, or where plumbing codes prohibit it. Route to a
floor drain or equivalent for safety reasons.
p
Drain line should be routed to allow free flow of water.
Ensure adequate slope, no traps, and no kinks. A restricted
drain can cause cylinder water to over concentrate and
result in poor operation.
p
If a drain is not located near the humidifier use a
condensate pump rated for hot drain water.