HM700A1000

Drain Valve Cleaning

Always clean the drain valve before installing a new cylinder. 

Scale from the spent cylinder may have fallen into the drain 

valve and could prevent its proper operation. To properly clean 

the drain valve it must be removed and disassembled.

1.

Disconnect spade terminals from the drain valve.

2.

Remove the two screws holding the valve to the drain

pan.

3.

Squeeze the tabs of the spring clamp holding the hose

to the drain valve and slide it up the hose. Pull hose

from drain valve. Lift the drain valve from the drain pan.

4.

Unsnap red coil cap on solenoid and remove the sole-

noid from the valve.

5.

Loosen brass nut holding actuator to plastic housing

with a wrench and disassemble actuator.

6.

Clean actuator components and valve housing (inlet

port, outlet port, and cylinder port). Put new o-ring that

was supplied with new cylinder into valve.

7.

Reassemble actuator making sure tapered end of

spring is oriented as shown in Fig. 25. Tighten brass nut

1/4 turn past hand tight.

8.

Clean out end of hose and reattach to valve. Slide hose

clamp back in place and place valve into drain pan.

9.

Secure valve with 2 screws to drain pan.

Fig. 24. Drain valve.

Fig. 25. Drain valve actuator assembly.

Installing the New Cylinder

CAUTION

Make sure the new cylinder is a HM700ACYL2. Use 

of any other model or remanufactured cylinders 

will void the HM700 warranty.

1.

Insert cylinder into drain valve. Tilt cylinder forward and

fit end of steam hose to steam outlet. Tip cylinder back

into place.

2.

Tighten hose clamp being careful not to over tighten and

crush the plastic cylinder steam outlet.

3.

Attach color-coded cylinder plugs to the corresponding

color-coded cylinder pin. Push down completely.

Connect high water sensor plug. Spring-loaded plugs

should fit snuggly onto the cylinder pin. Replace if they

are loose or damaged.

4.

Re-fasten tie strap.

5.

Replace the humidifier cover and secure with two

screws.

6.

Turn on power to humidifier with the external

disconnect.

7.

Open supply water shut off valve.

8.

Turn the humidifier On/Off /Drain switch to On.

Extended Shutdown

Should it be required to disconnect power to the humidifier for 

a period of extended shut-down, always drain the cylinder first.

1.

Switch the On/Off/Drain Switch to the Drain position.

2.

Wait until the humidifier is completely drained (usually

takes less than 10 minutes).

3.

Turn the On/Off /Drain switch to the off position.

4.

Shut off power to the humidifier with the external

disconnect.

5.

Close the supply water shut-off valve.

NOTE: As long as the HM700 is powered, it will 

automatically drain the cylinder when there has 

not been a call for humidity for an extended 

period of time. This feature will reduce or prevent 

the possibility of corrosion of the electrodes and 

the accumulation of algae and bacteria growing 

in the cylinder. The cylinder will remain empty 

until there is a call for humidity at which time the 

fill valve will open and refill the cylinder. The unit 

will go through its normal process for optimum 

operation.

STARTING AFTER EXTENDED SHUTDOWN

1.

Check to see the humidifier has not been damaged and

the installation has not been altered. See 

n

Start Up

Procedure

o

 on page 14.

2.

Turn on the power to the humidifier with the external

disconnect.

3.

Turn the On/Off/ Drain switch to the Drain position.

4.

Wait until there is no water flowing to drain. It usually

takes less than 10 minutes.

5.

Follow the start up procedure on page 14.

'=0-2()64368
%2(36-2+

+6392(
;-6)

730)23-(

74%()
'322)'8367

&6%77298
%'89%836

7'6);7

,37)%2(
,37)'0%14

1

1

70)):)%2(
730)23-(

746-2+
238)36-)28%8-32

4092+)6

%'89%836

Summary of Contents for HM700 Series

Page 1: ...Electrode Steam Humidifier klimaireINTL klimaireINTL com 1 647 477 3333 1 646 808 0240 KLIMAIRE International www klimaireINTL com HM700 Series IOM Manual...

Page 2: ...onditions without the need to change its configuration NOTE Because the humidifier is factory configured for optimal performance Honeywell strongly discourages changes to the jumpers or the potentiome...

Page 3: ...g can occur Do not mount on vibrating surface Do not mount on floor The HM700 produces steam at atmospheric pressure No devices which could block steam output should be connected to the steam outlet S...

Page 4: ...ll automatically fill to a higher water level to maintain full capacity during the life of the cylinder Eventually because of scale formation it will no longer be possible for the humidifier to reach...

Page 5: ...n run on 240 V See Figure 16 for details on configuring the HM700 to run on a different voltage Table 3 contains AHRI recommendations for humidity requirements and Table 4 shows what humidifiers and o...

Page 6: ...umidifier at a height convenient for servicing NOTE Do not mount on hot surfaces where freezing can occur vibrating surface or floor Mounting with Keyholes 1 The HM700 humidifier is wall mounted using...

Page 7: ...conductivity p Supply water should be cold 34 to 68 F 1 to 20 C p Install water shut off valve before humidifier to facilitate servicing p The drain line should not end in a sink used frequently by pe...

Page 8: ...ibution line Table 5 Steam distributor Fig 6 Fig 7 Fig 8 Distributor installed horizontally in a horizontal duct Fig 9 Distributor installed horizontally in a vertical duct Rotate the distributor 45 s...

Page 9: ...r the copper tube Fasten in place with the spring clamp Fig 11 Condensate return MAIN RULES FOR ATMOSPHERIC STEAM LINES p Steam lines must not have any restrictions which could result in back pressure...

Page 10: ...se Measurements in inches mm Fig 15 Common steam line installation errors Measurements in inches mm 1 1 2 191 36 2 2 1 2 191 6 97 32 27 8 0 2 7944368 6 87 1 2 191 322 8 78 1 37 83 0 2 6 32 27 8 0 2 1...

Page 11: ...instructions are not followed CAUTION JUMPER WIRE INSTALLATION p DO NOT install mains voltage wire hot or neutral into 120 or 240 terminal p DO install mains wires into L1 terminal hot and P terminal...

Page 12: ...allation or when it is not possible to retrofit a GFI circuit See Fig 24 for the location of green wire on the drain valve r Ensure that adequate power is available to carry full humidifier amp draw a...

Page 13: ...uct preferred or in room being humidified p Avoid placing near discharge diffuser of humidified air p Mount in area representative of room humidity drafts doorways sunlight or an overhang such as a sh...

Page 14: ...n Off humidifier It will run when 24 VAC from terminal 1 is fed back into terminal 2 through an On Off humidistat and other security devices in series 97 7 322 8 366 8 308 147 4 7 4 6 74 0 0 348 32 0...

Page 15: ...normal operation mode 7 Check and adjust the control setpoint on the control and high limit humidistat 8 When the external humidistat generates a demand for humidity and the security loop is closed t...

Page 16: ...icates steam is being produced Selecting a Relative Humidity Setpoint The optimum humidity setpoint depends on the reasons that a space is being humidified The nASHRAE Handbook HVAC Applicationso reco...

Page 17: ...om humidifier Control Board Controls all functions of the humidifier operation and provides input and output connections to humidifier components Fill Cup Provides an air gap for backflow prevention F...

Page 18: ...y result in damage to the humidifier Honeywell is not responsible for any damages resulting from or attributed to the failure to replace a spent cylinder see Manufacturerms Warranty NOTE Honeywell rec...

Page 19: ...r to the humidifier with the external discon nect 5 Remove the two screws securing the front cover 6 Remove the cylinder plugs from the cylinder pins by pulling vertically 7 Using a flat screwdriver l...

Page 20: ...der pin Push down completely Connect high water sensor plug Spring loaded plugs should fit snuggly onto the cylinder pin Replace if they are loose or damaged 4 Re fasten tie strap 5 Replace the humidi...

Page 21: ...ls that were provided with the auxiliary equipment and to Table 8 nTroubleshooting HM700 Faults o on page 22 Table 7 General troubleshooting Symptom Cause Corrective Action s Nothing happens when On O...

Page 22: ...Incorrect steam line installation Check that steam line has been installed with condensate traps and slope See nSteam Lines and Condensate Return Instructionso on page 8 Condensation in duct Installat...

Page 23: ...wn the potentiometer Wrong cylinder installed Install correct cylinder model Cylinder Spent but not detected by software Replace the cylinder see maintenance chapter Condensate from other source Remov...

Page 24: ...438 28 31 8 6 4 8 6 4 4 4 4 4 4 4 147 8 62 0 28 62 0 32 3 6 2 7 8 86 27 361 6 78 897 0 147 238 278 00 914 6 631 483 8 61 2 0 366 7432 2 83 1 27 308 238 6 43 287 36 962 2 2 0 4 038 328630 320 836 278...

Page 25: ...Configuraci n del humidificador El HM700 viene configurado de f brica para funcionar en la mayor a de las condiciones sin la necesidad de cambiar los par metros NOTA Como el humidificador viene confi...

Page 26: ...sale del humidificador puede estar muy caliente No vierta el agua por un fregadero p blico Todos los trabajos de plomer a deben realizarse conforme a los c digos de plomer a locales y nacionales PREC...

Page 27: ...ccesorio N mero de pieza Cilindro de reemplazo HM700ACYL2 Higrostato HumidiPRO H6062A1000 Kit de distribuci n de acero inoxidable con montaje a distancia HM700ADISTKIT V lvula de desag e de reemplazo...

Page 28: ...umidificador se llenar autom ticamente con un nivel superior de agua a fin de mantener la capacidad completa durante la vida til del cilindro Eventualmente debido a la formaci n de incrustaciones el h...

Page 29: ...guraci n del HM700 para que funcione con una tensi n diferente consulte la Figura 16 La Tabla 3 incluye las recomendaciones del Instituto de Aire Acondicionado Calefacci n y Refrigeraci n AHRI con res...

Page 30: ...umidificador HM700 se monta en la pared a trav s de una bocallave ubicada en la parte posterior de la ebanister a de la unidad 2 Use 8 tornillos de 2 in 5 cm montados en pernos 2x4 o m s largos Se nec...

Page 31: ...ratura de 34 a 68 F de 1 a 20 C p Para facilitar el mantenimiento instale la v lvula de cierre de agua antes que el humidificador p La l nea de desag e no debe finalizar en un fregadero utilizado frec...

Page 32: ...a 5 Distribuidor de vapor Fig 6 Fig 7 Fig 8 Distribuidor instalado horizontalmente en un conducto horizontal Fig 9 Distribuidor instalado horizontalmente en un conducto vertical Gire el distribuidor 4...

Page 33: ...ensado REGLAS FUNDAMENTALES PARA LAS L NEAS DE VAPOR ATMOSF RICO p Las l neas de vapor no deben presentar obstrucciones que puedan generar una contrapresi n p Tenga en cuenta los materiales las dimens...

Page 34: ...uera Dimensiones en pulgadas mm Fig 15 Errores comunes durante la instalaci n de la l nea de vapor Dimensiones en pulgadas mm 17 6 3 1 2 13 28 7 96 6 3 1 2 13 0 2 32 27 3 734368 7 313 1 2 13 32 8 6 0...

Page 35: ...NTE p NO instale el cable de voltaje de la red el ctrica activo o neutro en el terminal de 120 o 240 p INSTALE los cables de la red el ctrica en el terminal L1 activo y en el terminal P activo neutro...

Page 36: ...uptor diferencial Consulte la Fig 24 para ver la ubicaci n del cable verde en la v lvula de desag e r Aseg rese de contar con la alimentaci n adecuada que proporcione el amperaje completo para el humi...

Page 37: ...en la habitaci n humidificada p Evite colocarlo cerca de un difusor de descarga de aire humidificado p Inst lelo en un rea representativa de la humedad de la habitaci n las corrientes las puertas la...

Page 38: ...l terminal 1 al terminal 2 mediante un higrostato de encendido apagado y otros dispositivos de seguridad en serie 28 6694836 7 32 2 32 97 0 7 8 27 2 14 6 7 366 837 7 2 0 8 59 8 74 32 7 34 32 0 328630...

Page 39: ...i n de fallas p Despu s de la prueba del sistema el humidificador se encuentra en modo de funcionamiento normal 7 Controle y ajuste el punto de referencia de control en el control y en el higrostato d...

Page 40: ...r un punto de referencia de humedad relativa El punto de referencia ptimo de la humedad depende de los motivos por los cuales un espacio necesita ser humidificado El nASHRAE Handbook HVAC Applications...

Page 41: ...l Controla todas las funciones del humidificador y brinda conexiones de entrada y salida a los componentes del humidificador Recipiente de llenado Brinda un espacio de aire para evitar el reflujo V lv...

Page 42: ...oneywell no se hace responsable por los da os ocasionados como resultado de o atribuidos a la falta de reemplazo de un cilindro desgastado consultar la secci n nGarant a del fabricanteo NOTA El HM700...

Page 43: ...idificador a trav s del interruptor de desconexi n externo 5 Quite los dos tornillos que fijan la cubierta frontal 6 Para quitar los enchufes del cilindro de las clavijas jale de forma vertical 7 Con...

Page 44: ...a abrazadera de la manguera hasta colocarla en su lugar y ubique la v lvula en la bandeja de desag e 9 Fije la v lvula a la bandeja de desag e con 2 tornillos Fig 24 V lvula de desag e Fig 25 Ensamble...

Page 45: ...s est encendido Esta funci n reducir o evitar la formaci n de corrosi n en los electrodos y la acumulaci n de algas y bacterias en el cilindro El cilindro permanecer vac o hasta que se registre una de...

Page 46: ...nerales Problema Causa Medidas correctivas No hay actividad cuando se enciende el interruptor de encendido apagado El fusible est quemado Controle el fusible en l nea ubicado entre el transformador y...

Page 47: ...erifique que la l nea de vapor se haya instalado con sifones de condensado y presente la inclinaci n adecuada Consulte pInstrucciones de retorno del condensado y las l neas de vaporq en la p gina 9 El...

Page 48: ...ro de agua b Contacte a un representante de Honeywell para obtener recomendaciones El ciclo de humidificador es corto a Verifique si el higrostato de l mite alto u otro control de encendido apagado se...

Page 49: ...lindro no est instalado correctamente Verifique que los colores de los enchufes del cilindro coincidan con los indicadores que se encuentran junto a los electrodos en el cilindro adem s compruebe que...

Page 50: ...4 14 6 37 8 623 28 623 28 6694836 2 2 3 4 3 7 j 86 27 361 36 0 14 6 7 2 36 7 78 3 238 278 0 0 49 28 32 2 7 0 8 61 2 0 483 366 7432 28 0 8 27 2 46 2 4 0 238 492837 7 37 4 6 0 28 0 36 0 7 78 1 0 2 0 8 3...

Reviews: