AC Input Source and AC Branch Breaker:
•
Standard AC Input wire is required for all the AC connections between the AC source & the AC
Input port, and the AC Output ports to load.
•
For 120V model minimum of #10 AWG AC wire is required, A 30A branch circuit breaker is also
required to connect between AC Input source and unit’s AC Input port.
•
For 230V model minimum of #14 AWG AC wire is required, A 16A branch circuit breaker is also
required to connect between AC Input source and unit’s AC Input port.
Important: Follow the electrical and/or building code when you connect the unit to any AC source.
Installing the Inverter System
WARNING
:
Electrical Shock Hazard
The unit ‘On/Off’ switch does not disconnect the DC power from the battery. Use the DC
Disconnect Switch or disconnect the DC input cables to disconnect the DC power from the
battery before working on any circuits connected to the unit. Failure to follow these
instructions can result in death or serious injury.
Installation:
•
Choose an appropriate mounting location.
•
For indoor use, the unit can be mounted in any direction except with the DC Input panel facing
downwards.
•
Use the mounting template below to mark the positions of the mounting screws.
•
Drill the 4 mounting holes and place the Inverter in position and fasten the unit to the mounting
surface.
Important: Field wiring DC terminals tightening torque 12-13 Nm
Chassis Grounding Connection:
DANGER:
The unit chassis has to be grounded properly. Never operate the Inverter
without proper grounding. Failure to do so will result in death or serious injury.
•
Connect the grounding cable’s ring terminal to the unit ground screw.
•
Connect the other side of the cable to the common grounding point.