Page 12
E05
Input battery voltage is low and
warning occurs
Recharge battery as unit will shutdown
shortly
E06
At Battery Mode, AC output load
connected has sensed high and is
close to shutdown limit
Reduce load
E07
Internal temperature is high and is
close to shutdown limit
Reduce load and check if any ventilation
of the unit is blocked
E08-11 Not
used
E12 Internal
transfer
switch
temperature is high and shutdown
occurs
Reduce load and check if any ventilation
of the unit is blocked
AC Load on Inverter
Although the Power Inverter can provide high surge power up to two times the rated output power,
some high surge loads like sump-pumps, heavy duty motors etc. may still trigger the inverter
protection system even though the load falls within the power rating of the inverter. A higher power
Inverter is required for these appliances.
Important: For SWXFR1230 (3000W Inverter), each 3-pin AC socket provided can only provide
20A AC current. For (NEMA 5-20) a single appliance that requires more than 20A AC Input
(>2400W) power, it is required to hardwire to the AC Output port 3 or 4.
Estimated Run Time
Following run times are estimates for reference, based on using different battery bank sizes.
Actual run times may vary.
Important: Power Drain From DC Battery Bank.
Please noted that when the SWXFR1230 is running in AC Bypass mode, there is a power drain of
about 700mA from the battery bank connected to the DC Input of the unit. A battery charger with
sufficient power is required to maintain the battery bank voltage.
Estimate run time on different 12V Battery Bank Size
AC Load
60AH 120AH 180AH 240AH 300AH
50 W
11 hrs.
22 hrs.
33 hrs.
44 hrs.
55 hrs.
100 W
5 hrs.
11.5 hrs.
17 hrs.
23 hrs.
29 hrs.
200 W
2.5 hrs.
5 hrs.
8 hrs.
11 hrs.
13.5 hrs.
500 W
49 mins
2 hrs.
3 hrs.
4 hrs.
5 hrs.
1000 W
15 mins
49 mins
1.5 hrs.
2 hrs.
2.5 hrs.
1500 W
8 mins
27 mins
49 mins
1 hr
1.5 hrs
2000 W
N.R.
15 mins
34 mins
49 mins
1 hrs
2500 W
N.R.
11 mins
25 mins
37 mins
49 mins
3000 W
N.R.
N.R.
17 mins
27 mins
37 mins
Note: N.R. - Not Recommended
5. FEATURE
SETTING
To understand more about the unit features, read the following section and follow the instructions
to make changes to the desired setting.
Default Factory Setting:
PS (Inverter):
PS1 - inverter enabled in standby mode with load sense off
AL (Alarm):
AL1 - alarm enabled
Sd (UV shutdown): SdL - Under voltage shutdown set to low setting
Cb (Current Setting): Cb3 – Maximum AC Input Branch Breaker Setting
Understanding the Unit Settings
Inverter Setting