1. Safety Information
2. Parts Name and Control Unit
2.1 Generator fig
2.2 Control Panel
2.3 Breaker
2.4 Fuel Meter
2.5
2.6 AC Three-phase and Single-phase Output Terminals
3. Pre-running Check
3.1 Engine Oil
3.2 Fuel
3.3 Coolant
3.4 Fuel-water Separator
3.5 Battery
4. Start and shut off the engine
4.1 Break-in Period (initial 50 hours)
4.2 Start the Engine
4.3 Stop the Engine
The functions of the digital panel
1
2
2
3
4
4
5
6
7
8
9
11
12
13
14
14
14
16
CONTENTS
38
The conditions of generator rated output:
Altitude: 0 m Ambient temperature: 25 Relative humidity: 30%
Ambient modified coefficient: C (Relative humidity 30%)
Note: When the relative humidity is 60%, the modified coefficient is C-0.01
When the relative humidity is 80%, the modified coefficient is C-0.02
When the relative humidity is 90%, the modified coefficient is C-0.03
When the relative humidity is 100%, the modified coefficient is C-0.04
Counting example:
When the rated power of generator is P =5KW, altitude is 1000m, ambient
N
temperature is 35
, relative humidity is 80%, the rated power of generator is:
P=P
(C-0.02) = 5
(0.82-0.02) = 4KW
N
2. Modified coefficient table of ambient condition power
Ambient temperature (
)
Altitude
(m)
0
500
1000
2000
3000
4000
25
1
0.93
0.87
0.75
0.64
0.54
30
0.98
0.91
0.85
0.73
0.62
0.52
35
0.96
0.89
0.82
0.71
0.6
0.5
40
0.93
0.87
0.80
0.69
0.58
0.48
45
0.90
0.84
0.78
0.66
0.56
0.46