54
01/13424999894
Technical data
The power supplies and electrical control equipment are to be operated exclusively with the components authorised by
the manufacturer.
Electrical properties
Primary energy supply
Power supply voltage:
230 V AC nominal (-10 % / +10 %)
Power consumption:
approx. 260 W
Power consumption (standby):
approx. 7 W
Connecting terminal:
max. 2.5 mm², spring terminal
Mains fuse:
micro-fuse 5 x 20, 3.15 A/T
Class of protection: class
I
in accordance with DIN EN 61140 (VDE 0140-1)
Output
Voltage:
27.5
V
nominal
Ripple:
0.3
V
ss
Current:
8 amp, 30 % ED in relation to 10 min
Current (for a short time):
10 amp for 400 ms
Opening / closing sequence:
reversal of voltage polarity
Pause time during change of polarity:
variable according to actuation behaviour
Automatic activation:
after 180 sec, can be disconnected via jumper for the drives for the duration
of
the
mains
failure
function
Connecting terminal:
max. 6 mm², spring terminal
Max. number:
in accordance with max. current draw of the drives
Fuse:
FKS
10A/
32
V
Wind rain detector output
Voltage:
27.5
V
nominal
Power:
max. 100 mA, 100 % ED
Terminal:
max. 1.5 mm², screw terminal
Cable monitoring function:
no
Max. number:
depending on the current consumption
Fuse:
via
motor
fuse
Output for further components, e.g. temperature sensor
Voltage:
27.5
V
nominal
Power:
max. 500 mA, 100 % ED
Terminal:
max. 1.5 mm², screw terminal
Cable monitoring function:
no
Max. number:
see
technical
documentation
Fuse:
via
motor
fuse
potential free contact:
1 amp / 60 V DC
Mechanical properties
Dimensions:
188 x 130 x 278 mm, without screwing, (w x h x d)
Weight:
approx.
1.8
kg
Circuit connections and operation
Connection:
see
technical
documentation
Suitable
for
SHE:
no
Suitable for ventilation:
yes
Ventilation function during mains
power
failure:
no
Maintenance
counter:
no
Ventilation control panel iVent 8A