GL0016P-02 Installation Guidelines for BioDisc

®

 Units BF, BG, NF & NG 

 

 

6

 

GENERAL CONCRETE SPECIFICATION  

IN ACCORDANCE WITH  BS EN 206-1 ( BS 8500-1) 

TYPE OF MIX 

(DC)  DESIGN 

PERMITTED TYPE OF CEMENT 

BS 12 (OPC): BS 12 (RHPC): BS 4027 (SRPC) 

PERMITTED TYPE OF AGGREGATE 
(coarse & fine) 

BS 882 

NOMINAL MAXIMUM SIZE OF AGGREGATE 

20 mm 

GRADES:                     C25 /30 
                                     C25 /30  
                                     C16 /20 

REINFORCED & ABOVE GROUND WITH HOLDING 
DOWN BOLTS 
REINFORCED (EG. FOR HIGH WATER TABLE) 
UNREINFORCED (NORMAL CONDITIONS) 

MINIMUM CEMENT 
CONTENT 

C30 
C20 

270 - 280 Kg/M

3

 

220 - 230 Kg/M

3

 

SLUMP CLASS 

S1 (25mm) 

RATE OF SAMPLING 

READY MIX CONCRETE SHOULD BE SUPPLIED 
COMPLETE WITH APPROPRIATE DELIVERY 
TICKET IN ACCORDANCE WITH BS EN 12350-1 

                                       

NOTE:  STANDARD MIXES SHOULD NOT BE USED WHERE SULPHATES 

                             OR OTHER AGGRESSIVE CHEMICALS EXIST IN GROUND WATER

 

 

5.0 BioDisc Installation 

5.1   Remove the package tied to the outside of the unit. This contains a cover key. 
5.2   Excavate a hole of sufficient length and width to accommodate the unit and a minimum of 150mm 

concrete surround and to a depth which allows for the burial depth of the unit plus a minimum 150mm 
thick concrete base.  

5.3   Construct a suitable concrete base slab, a minimum of 150 mm thick, appropriate to site conditions.  

In wet or unstable ground conditions it may be necessary to lay a hard-core sub-base (see notes 3.3 & 
4.3). Ensure that the slab is flat and level. Allow the slab to set sufficiently to support the installed load, 
but not so much as to prevent subsequent backfill bonding fully to the base.  

5.4   Ensure that the slab is free of any stones or other material which could damage the unit. Lower the 

unit onto the slab using suitable webbing slings and lifting equipment.

 

5.5   Remove the covers by undoing the locks and folding the end covers back over the inner covers before 

lifting them off. 

5.6   Remove the Control Panel and Owners Pack from the walkway inside the unit. 
5.7   Check that the inlet and outlet orientation is correct and that the unit is level. It is essential that the unit 

is installed in a level plane to avoid undue stress on the bearings.  
The rotor shaft must be level end to end, to within ±3mm, measured at the bearing caps or directly on 
the shaft. 
The unit must also be level to within ±5mm from side to side, measured at the GRP walkway on either 
side of the rotor. 
If necessary, lift the unit off the base and apply further concrete as needed to level up. 
Note :  The top flange of the BioDisc should not be used for levelling as manufacturing tolerances may 
result in it not being parallel with the rotor shaft. 

5.8   It is essential that levels given above are checked regularly throughout the installation process. Should 

the unit become out of level, immediate remedial action is advised, to maintain the unit within the 
levels stated in section 5.7.   

5.9   Pour no more than 1 metre depth of water into both primary (inlet) chambers and the final (outlet) 

chamber ensuring  that there is never more than 250mm difference in water level between any of the 
sections. 

Summary of Contents for BF BIODISC

Page 1: ...ith in the control panel housing If additional copies are required contact Kingspan 510030P BF 3 Phase Control Panel Wiring Diagram 510003P BF 3 Phase Alarm Control Panel Wiring Diagram 510017P BF Sin...

Page 2: ...tails on request Should you wish to inspect the operation of the equipment please observe all necessary precautions including those listed below which apply to maintenance procedures BioDisc units con...

Page 3: ...GL0016P 02 Installation Guidelines for BioDisc Units BF BG NF NG 3...

Page 4: ...also inside units particularly if they have been stored on site prior to installation adding weight and increasing instability Check units before lifting and pump out any excess water 2 5 When lifting...

Page 5: ...though not obligatory for an installation of this type RCD protection is suggested as an extra precaution 3 12 Pump stations or any other associated equipment should have a separate power supply 3 13...

Page 6: ...support the installed load but not so much as to prevent subsequent backfill bonding fully to the base 5 4 Ensure that the slab is free of any stones or other material which could damage the unit Low...

Page 7: ...panel Customer Supply Inlet Pipe Control Panel G L 600mm Inlet Invert Add 100mm For Outlet Invert Concrete backfill minimum 150mm thick but to suit specific site conditions Concrete Pea Shingle or oth...

Page 8: ...control panel should be positioned adjacent to the unit so that a It does not interfere with cover removal b It is convenient for the incoming power supply c It cannot be reached by someone standing i...

Page 9: ...han 100 metres from the BioDisc and that the interconnecting cable customer supply should be laid in a separate trench to prevent electrical interference 6 2 5 Connect the incoming power supply to the...

Page 10: ...GL0016P 02 Installation Guidelines for BioDisc Units BF BG NF NG 10...

Reviews: