General Vent Installation Information
Installation Of Side Wall Venting
1. The minimum distance from the bottom of fireplace to centre of vent is 44.5 inch
(130 cm) (See Figure 1). Cut a hole through the wall allowing for a 11” x 11” (inside diame-
ter) in combustible walls for wall thimble or an 8” diameter hole in a non-COMBUSTIBLE
wall (See Figure 2).
2. Note clearance to combustible as stated on pages 7 & 8.
3. Select the approximate vent length, precise measurements are not needed as your flex
pipe can be expanded to twice its shipped length for ease of installation.
4. To install wall thimble centre over 11” x 11” (inch) framing from both sides of wall and
secure. Route flex vent pipe through wall thimble (See Figure 1).
5. Before joining pipes, apply a bead of high temperature sealant (Mill Pac) to end of pipe.
First attach the four inch (4”) flue pipe to the vent termination with sealant, and secure with
4 screws provided. At this time make sure the spacer springs are attached to the (4”) flex
pipe as required. Then attach the seven inch (7”) pipe by the same method.
6. Mount vent termination and seal to wall using caulking around the wall thimble to weather
proof. After installing the vent termination, double check to make sure the pipe extends
properly through wall thimble and into vent termination.
7. Before joining pipes to fireplace flue, apply a bead of high temperature sealant (Mill Pac) to
end of pipe. First attach the four inch (4”) flue pipe to fireplace with Mill Pac sealant to the
flue pipe and secure with 4 screws provided. At this time verify that the spacer springs are
attached properly to the (4”) flex pipe as required. Then attach the seven inch (7”) pipe by
the same method.
8. Support horizontal pipes every two (2) feet (61 cm) with metal strap bands. Re-check fire-
place to make sure it is levelled and properly positioned and secured.
9. Support vertical pipes to maintain a minimum of 1” or greater clearance to combustibles
with metal strapping bands.
10. If finishing the outside wall with vinyl or wood siding it is recommended that a Siding
Shield be installed, Part Number ZDVSSLR.
Note: Wall Thimble cover combustible wall up to 11” thick.
Note: Venting termination must not be recessed into wall or siding.
FIGURE 2
FRAMING DETAIL
11.0"
11.0"
8" DIA
44.5" TO CENTERS
MINIMUM
THROUGH COMBUSTIBLE
WALL
THROUGH
NON-COMBUSTIBLE WALL
TOP OF ENCLOSURE
With insulation
sleeve
50.5”
43 1/16”
44.5”
2 1/2”
18.875”
0.500”
Gyprock facing
NOTE:
1/4” RISE PER
FOOT OF
HORIZONTAL
RUN
Louvered Unit Shown
RIGID OR HARD PIPE
When using Simpson Duravent, AmeriVent pipe, ICC Excel Direct, Metal Fab Sure-Seal DV and or
Selkirk Direct Temp a Duravent hardpipe adapter must be used (
part # ZDVDFA for fireplaces and
part # ZDVDKA for Stoves, Serenity and ZDV3624B
). Follow installation instructions provided by
Simpson Duravent/AmeriVent/Selkirk Direct Temp, ICC Excel Direct, Metal Fab Sure-Seal DV for
installation of pipe and adhere to the clearance to combustibles provided in this manual. Apply a bead of
Mill Pac high temp sealant to all joints of pipes, adapters and termination, when using Kingsman Flex(Z-
Flex)Venting venting and Simpson Duravent venting.
NOTE:
Increase framing depth by one inch when using hardpipe.
Flex Pipe Venting
Kingsman Flex pipe is shipped in unexpanded length. When installing pipe expand the lengths. Pipe can
be expanded to twice their lengths e.g. 4ft. to 8ft. Fully expand pipe and cut off excess.
Do not use more than 2 couplers to extend short pipes. Single sections are preferred in an installation
attaching at the fireplace and termination.
Place the spring spaces provided approximately every two feet to stabilize 4” flex in the center of 7” flex.
When forming bends place spring in bend or before and after. (See Fig. 1).
Horizontal runs require support metal straps every 2 feet. In off set installation support straps should be
used to stabilize pipe.
Expand 4” and 7” flex pipe to the point that the 7” protrudes approximately 2 to 3 inches past outer wall and
the 4” flex protrudes approximately 2 to 3 inches past the 7” flex. See Fig. 1. Attach the 4” pipe to the termi-
nation first and secure with sealant and four screws then attach the 7” flex to the termination with caulking
and four screws. Termination may then be moved back to the outer wall and attached to home screwing
into the framing. Silicone around termination to waterproof. If siding shield is going to be used attach this
using same attaching hole as the top of termination after termination has been caulked for water proofing.
Use Hi Temp Sealant
Apply a bead of mill pac high temp sealant to all joints and use four screws to secure each pipe at fire-
place, termination and any joint if joining any sections of pipe.
NOTE:
It is critical to the proper and safe operation of this
fireplace that on all connections the inner liner and the
outer casing are both caulked with liberal amounts of
sealant. Do not use any kind of tape or silicone other than
that recommended in this manual, Mill Pac Sealant
FRAMING DIMENSION
Combustible Wall
Cut a 11” hole through exterior wall and frame as
shown below.
Non combustible Wall
Cut or drill 8” or 204mm diameter hole.
OPTIONAL
CLAMPS
FIGURE 1
MAX. DISTANCE BETWEEN SPACERS 2 FEET
SPRING SPACERS
OPTIONAL
CLAMPS
SEAL WITH HIGH TEMP. SEALANT
SEAL WITH HIGH TEMP. SEALANT
This gas appliance is approved to be vented either through the side wall or vertically through the roof.
Only Kingsman Flex(Z-Flex)Venting Kits and components
specifically approved and LABELED for this stove may be used
. This appliance is also approved for use with Simpson-Duravent Direct Vent system (Model DV-
GS Series), Ameri-Vent Direct Vent Pipe System, ICC Excel Direct, Metal Fab Sure-Seal DV and Selkirk Direct Temp.
WARNING:
DO NOT mix parts from different systems unless
stated in the manual.
32
Summary of Contents for HBZDV4740
Page 23: ...Gas Conversion for Modulator PART C WARNING WARNING 23 ...
Page 26: ...Configuration 1 Basic manual HI LO and manual ON OFF capabilities 26 ...
Page 27: ...Receiver Module 584 523 521 221 1001 P221SI Receiver Module 584 523 521 221 1001 P221SI 27 ...
Page 28: ...Receiver Module 584 523 521 221 1001 P221SI Receiver Module 584 523 521 221 1001 P221SI 28 ...