(4). When the drain pipe is used for multiple devices, the public section of the pipe should be
100mm lower than the drain hole of each device and it is better to use the much thicker
pipe for such a purpose.
3.10 Installation of the Drain Pipe
(1). The diameter of the drain pipe should be larger than or equal to that of the refrigerant pipe
(PVC pipe, outer dimater:25mm, wall thickness
≥
1.5mm.
(2).
The drain pipe should be as short as possible and with at least a 1/100 degree of slope to
avoid forming air pockets.
(3). If the proper degree of slope of the drain pipe is not allowed, a lift pipe should be installed.
(4). A distance 1-1.5m should be kept between the hangers to avoid the drain hose making a
turn.
1~1.5m
(Right) with a min. degree of slope 1/100
(Wrong)
Fig.14
(5). Insert the drain hose into the drain hole and tighten it with clamps.
(6). Wrap the clamps with large amount of sponge for thermal insulation.
(7). The drain hose inside the room also should be insulated.
Clamp (accessory)
Sponge (gray)
Drain Hose
Sponge (accessory)
Clamp
(accessory)
Max. 4mm
Fig.15