Page 23 of 56
King Pigeon Hi-Tech. Co., Ltd.
Ver 2.3
Industrial Ethernet Remote I/O Module
IoT Data Acquisition Module
file, convenient for next configuration.
Language Selection
[Chinese]:
Click to switch language to Chinese.
[English]:
Click to switch language to English.
7.3 Basic Setting
Device ID:
Default is 1, can be 1~247.
Device Information:
Max 32 characters, this is the description of the module, e.g.: installation address, usage
instructions and so on.
AIN Setting:
0~5V,0~10V,0~20mA,4~20mA are optional, After selecting the specific mode, you also need to set the
AIN switch to the corresponding position on the hardware; [Maximum value] and [Minimum value]
are the sensor range, and [Current value] will be automatically converted to the real value according
to the set range.
DIN setting:
Can choose normal mode or counting mode; DIN1 supports high-speed pulse and low-speed pulse
mode, the default is that the maximum high-speed pulse frequency is 700KHz, and the maximum
optional low-speed pulse frequency is 10KHz. DIN2~DIN12 can be used as low-speed pulse counters:
the anti-shake time can be set from 1 to 2000ms, the default is 1ms, and the corresponding pulse
frequency is up to 1KHz.
DIN Input Status:
The state of the digital input. When the state of the digital input is closed, the corresponding
value in the list is 1, otherwise it is 0.
DIN1 Counter Default Trigger Direction:
Can be set as rising edge or falling edge, need restart to take effect.
DO Output Status:
The Digital output status, when the status of the digital output is closed, the corresponding,
value in the list is 1, otherwise it is 0. Double-click the value of a specific DO to change it, and
the corresponding DO will immediately output related actions;
Click [Turn On] or [Turn Off], all DO will output related actions immediately.
DO1 Pulse Output ,DO2 Direction Control:
Tick ”Enable”, stands for DO1 is used as pulse output and DO2 is used
as direction control after the device restarts.