Devices connectable to the control unit
DIP4 set to OFF:
- during the closing phase they lock the movement and re-open the
door fully when released
- during the opening phase they do not intervene
- with the opened door they lock closing commands
- with the door closed they allow opening
Figures 38a, 38b and 38c show examples of King Gates “Viky30”
photocell connections.
When multiple devices are connected on this contact, they
must be connected in series (see Fig. 38c)
.
If more photocell pairs are connected, RX and TX units of
the safety set should be cross installed (see Fig. 38c).
“S1 Edge” OPENING/CLOSING PHASE SAFETY DEVICES
It is possible to connect devices (e.g. photocells or edges) with nor-
mally closed (NC) contact or 8K2 resistive edges to the “S1 Edge”
input (terminal 9-10).
The factory wire bridge connected to PHO2 must be removed when
using this input.
These devices intervene while the door is moving, in particular:
- with the door closed they stop the opening commands.
- with the door open they stop the closing commands.
- during the closing phase they command a brief inversion
- during the opening phase they stop movement
Figures 38a, 38b and 38c show examples of King Gates “Viky30”
photocell connections.
When multiple devices are connected on this contact, they
must be series connected (see Fig. 38c).
If more photocell pairs are connected, RX and TX units of
the safety set should be cross installed (see Fig. 38c).
Connection of the TX
transmitter
Connection of the RX
receiver Viky30
+VA (8 or 10)
OV (7)
1 2
+VA (8 or 10)
0V (7)
S2 Photo (3) or
S1 Edge (9)
1 2 3 4 5
+VA (8 or 10)
38a
38b
1
2
3
4
5
6
7
8
9
10
14
13
L
N
10.2
10.5
10.4
10.3
10.3
10.6
10.1 - 10.2
10.1 -
Warning light
TERMINALS: 1-2.
The warning light is an accessory used for signaling any movement
of the gate leaf.
Connected lamps: 24V 15W maximum power.
10.2 -
AUX output contact
TERMINALS: 1-2 or 4-8.
Default setting: 24Vdc output for inductive loads (relay) not active at
the factory.
See paragraph 13 to activate the AUX output. By default, the AUX
output is bistable and is associated with the remote control key
memorized for this function.
10.3 -
Safety devices
TERMINALS: 3 (S2 Photo) and 9 (S1 Edge).
The control unit has two safety inputs available for voltage free (dry
contact) connection(s).
“S2 Photo” CLOSING or OPENING/CLOSING PHASE SAFETY
DEVICES
Terminal 3 allows the connection of safety devices active
during the closing and opening phases. This input is normally closed
(NC). For infrared photocells and safety edges with micro-switch
contact. The factory wire bridge connected to S2 Photo must be
removed when using this input.
These devices intervene during the gate’s closing and opening phase
according to DIP switch 4 (see par. 4.1).
In particular:
DIP4 set to ON:
- during the closing phase, they stop the movement and reopen
when disengaged
- during the opening phase they stop the movement and reopen
when disengaged
- with the opened door they lock closing commands
- with the closed door they lock the opening commands.