Alarm / Protection Condition
Trigger Values
High Voltage Alarm for each Cell
3.55±0.03 V
High Voltage protection for each cell
3.65±0.03 V, Delay time: 1s
High Voltage release for each cell
3.40±0.03 V
High Voltage alarm for total voltage
56.6 V±0.5 V
High Voltage protection for total voltage
60.0 V±0.5 V, Delay time: 1s
High Voltage release for total voltage
54.4 V±0.5 V
High Voltage release method
Under the release voltage (54.4 V±0.5 V) for 1s
Low Displayed Capacity Alarm
10% of Capacity or lower
Low Voltage alarm for each cell
3.00±0.03 V
Low Voltage protection for each cell
2.70±0.03 V, Delay time: 1s
Low Voltage release for each cell
3.10±0.03 V
Low Voltage alarm for total voltage
48.0 V±0.5 V
Low Voltage protection for total voltage
45.5V±0.5 V, Delay time: 1s
Low Voltage release for total voltage
49.6 V±0.5 V
Low Voltage release method
Charge to recovery
Charge over current alarm
165±5 A
Charge over current protection
180±5 A, Delay time: 5s
Charge over current release method
Auto release after 1min
Discharge over current alarm
165±5 A
Discharge over current protection
180±10 A, Delay time: 1s