background image

8. Alarm Visual and Audible Indicators

If you require further information please contact Product Support at 

1-800-880-6788 or write us at: Kidde Canada Inc., P.O. Box 40, Apsley, ON 

K0L 1A0 or visit us on the web at www.kiddecanada.com.

Operational Mode

Visual  

Indications

Audible  

Indications

Note:

Initiating Alarm 

(Multiple alarms in 

an Interconnected 

system)

Green LED blinks once per 

second indicating that this 

is the unit initiating the 

alarm in an interconnected, 

multiple alarm, system. 
Red LED blink in time 

with alarm pattern.
Strobe will flash 1 time 

per second.
AC power must be applied - 

strobe will not operate with 

DC Only power applied.

3 long beeps, voice mes-

sage “Fire! Feu!”,3 long 

beeps, repeating.

Green LED operation of 

non-initiating alarms:
AC power applied:  On 

continuously.
DC Only power applied:  

Flash once every minute.
All P4010ACLEDSCA 

strobes in an 

interconnected 

system will flash in 

synchronization.

Low Battery

Amber LED blink 2 times 

per second – AC Power 

applied

Red LED blink in time 

with unit chirp every 

60s. Battery backup 

(DC only).

AC Power applied – Unit 

will chirp once a minute 

followed by the voice 

message “Low Battery. 

Pile Faible”

Battery Backup – Unit will 

chirp once a minute, the 

voice message “Low Bat-

tery. Pile Faible” will occur 

once every 15 minutes.

Ambient Light Sensor 

Feature – Inhibits Low 

Battery chirps during 

the night.

The alarm should be 

replaced as soon as 

possible.  See section 

11, Deactivation of 

Alarm, before disposing 

of alarm.

Fault Mode

Red LED will blink in time 

with unit chirp every 30 

seconds.  Separate from 

the fault blink, the amber 

LED will also flash a fault 

code every 30 seconds. 

The fault code can be 2 to 

14 flashes depending on 

the fault type.

Unit will chirp every  

30 seconds.

Remove, deactivate, and 

replace alarm as soon as 

possible.

End of Unit Life

Red LED blinks in time 

with unit chirp, 2 times 

every 30 seconds.

Unit will chirp 2 times 

every 30 seconds.

Ambient Light Sensor - 

Inhibits End of Unit Life 

chirps at night for the 

first 30 days of the End of 

Unit Life period.
Remove, deactivate, and 

replace alarm as soon as 

possible.”

End of Unit Life, Hush 

Mode

Red LED blinks once 

every 2 seconds.

None, End of Unit Life 

chirps silenced.

Pressing the Test/Hush 

button will silence the 

chirps for 3 days at a 

time for a maximum of 

30 days.  After 30 days, 

End of Unit Life chirps 

cannot be silenced.
Remove, deactivate, and 

replace alarm as soon as 

possible.

End of Unit Life, 

(30 days after End of 

Life chirps begin)

Red LED will blink in time 

with unit chirp 2 times 

every 30 seconds.

Unit will chirp 2 times 

every 30 seconds.

Remove, deactivate, and 

replace alarm as soon as 

possible.

Summary of Contents for P4010ACLEDSCA

Page 1: ...take a few minutes to thoroughly read this user guide which should be saved for future reference and passed on to any subsequent owner Photoelectric Smoke Alarm with LED Strobe and Voice User Guide SI...

Page 2: ...ese combustible products from the kitchen If the alarm sounds check for fires first If a fire is discovered follow these steps Become thoroughly familiar with these items and review with all family me...

Page 3: ...fire department from your cell phone outside or from your neighbor s home not from yours Don t return to your home until the fire officials say that it is all right to do so Do not reenter under any c...

Page 4: ...st Hush button on the initiating CO or Combination alarm unit will terminate the CO alarm on all interconnected units If the CO condition that caused the alarm in the first place continues the initiat...

Page 5: ...g less when the lives of your family are at stake Please take a few minutes to thoroughly read this user guide and save it for future reference Teach children how to respond to the alarms and that the...

Page 6: ...e by date 10 years from initial power up in permanent marker on the label prior to installing the unit Model Number P4010ACLEDSCA 3 wire interconnect unit Power 120 V AC 60Hz 863mA max wire in connect...

Page 7: ...t or Indirect and Supplementary Light Output 177 Candela minimum on axis measurement The following diagrams show that the light intensity gradually decreases as the viewing angle is increased Use this...

Page 8: ...s Photoelectric sensing alarms may detect visible fire particles associated with slow smouldering fires sooner than ionization alarms A battery powered alarm must have a battery of the specified type...

Page 9: ...arm in every Sleeping Room Locate an alarm in every room where electrical appliances are operated i e portable heaters or humidifiers Locate an alarm in every room where someone sleeps with the door c...

Page 10: ...OM FIRE EXTINGUISHERS SMOKE ALARMS CARBON MONOXIDE ALARMS SMOKE CO ALARM TOTAL HOME PROTECTION FIGURE 1C Install smoke alarms on sloped peaked or cathedral ceilings following the mounting guidelines o...

Page 11: ...IZONTAL DISTANCE FROM PEAK NOT IN THIS AREA ANYWHERE IN THIS AREA 0 9 m 3 MINIMUM BEST PLACEMENT S T A G N A N T A I R MINIMUM 10 cm 4 NEVER HERE ACCEPTABLE PLACEMENT 30 5 cm 12 MAXIMUM CEILING 10 cm...

Page 12: ...ection install at least one alarm close to the bedrooms For additional protection see Figure 1A WARNING Test your smoke alarm operation after mobile home has been in storage or unoccupied and at least...

Page 13: ...d be made by a qualified electrician and all wiring used shall be in accordance with codes having jurisdiction in your area The multiple station interconnect wiring to the alarms must be run in the sa...

Page 14: ...ll possible to interconnect up to a total of 6 remote signaling devices and or relay modules see below for details on interconnecting Kidde devices The following models can be interconnected using the...

Page 15: ...o signal that power has been applied and a voice message will prompt you to push the test button If AC power is on at this time confirm the green LED is on constant 2 Rotate the unit fully onto the mo...

Page 16: ...strobe do not activate the unit must be replaced Weekly testing is required to ensure proper operation Erratic or low volume sound or no sound or no strobe activation from your alarm may indicate a de...

Page 17: ...ction What to do when the alarm sounds Smoke Alarm activation CO Alarm from an interconnected CO or Combo unit this unit is not a CO alarm Red LED blinks in time with alarm pattern Strobe will flash 4...

Page 18: ...ssage Low Bat tery Pile Faible will occur once every 15 minutes Ambient Light Sensor Feature Inhibits Low Battery chirps during the night The alarm should be replaced as soon as possible See section 1...

Page 19: ...8 10 minutes This feature is to be used only when a known alarm condition such as smoke from cooking activates the alarm The smoke alarm is desensitized by pushing the Test Hush button on the initiat...

Page 20: ...This alarm is equipped with a low battery monitor circuit While powered by AC the amber LED will blink 2 times a second and the unit will chirp once a minute followed by the voice message Low Battery...

Page 21: ...ion of Alarm WARNING Failure to DEACTIVATE alarm as instructed prior to disposal may create potential for lithium battery related fire or hazard To Deactivate The Alarm Rotate the alarm counterclockwi...

Page 22: ...he alarm If the alarm is in Fault mode and the amber LED is blinking a fault code of 10 flashes the alarm may be in need of cleaning After cleaning press the Test Hush button If the fault does not cle...

Page 23: ...h the sound and visual signals of a smoke a carbon monoxide and or strobe alarm and train them to leave your home when they hear or see it Practice a fire drill at least every six months including fir...

Page 24: ...e Once outside go to your selected meeting place and make sure everyone is there Call the fire department from your neighbor s home not from yours Don t return to your home until the fire officials sa...

Page 25: ...ore Smoke Alarms Desirable Required number of smoke alarms as shown in Figure 1A and Figure 1B The required number of smoke alarms might not provide reliable early warning protection for those areas s...

Page 26: ...in duration to the above warranty period In no event shall the Manufacturer be liable for loss of use of this product or for any indirect special incidental or consequential damages or costs or expens...

Reviews: