background image

 

P/N 3102530-

EN • REV 001 • ISS 16OCT18 

 

3 / 4 

Installation 

Notes 

• 

This detector does not sense fires in areas where smoke cannot 
reach the detector. Smoke from fires in walls, roofs, or on the 
opposite side of closed doors may not reach the detector. 

• 

This detector does not detect oxygen levels or flames. Use this 
device as part of a broad-based life safety program which includes 
a variety of information sources pertaining to heat and smoke 
levels, extinguishment systems, visual and audible devices, and 
other safety measures. 

• 

Photoelectric detectors have a wide range of fire-sensing 
capabilities and are best suited for detecting slow, smoldering fires. 

• 

To ensure proper operation, store the detector within the 
recommended ranges. Allow the detector to stabilize to room 
temperature before applying power. 

• 

The dust cover (supplied) must remain on the detector during 
installation and be removed prior to commissioning and service. 
The dust cover is not a substitute for removing the detector during 
new construction or heavy remodeling. 

• 

Do not install detectors until after final construction cleanup (unless 
otherwise specified by the AHJ). 

• 

Do not use smoke detectors with detector guards unless the 
combination has been evaluated and found suitable. 

• 

Install per NFPA 72 

National Fire Alarm and Signaling Code

NFPA 720 

Standard for the Installation of Carbon Monoxide (CO) 

Detection and Warning Equipment

, and UL 2075 

Standard for Gas 

and Vapor Detectors and Sensors

• 

Upon completion of the original installation and following any 
modifications or additions to the system, perform a calibrated 
sensitivity test per NFPA code. The Signature Series can perform 
this test and generate a system sensitivity report. 

To install the detector: 

1.  Install and wire the base, as described on the installation sheet 

supplied with the base. 

2.  Set the detector address.  Refer to the panel technical reference 

manual for a list of valid addresses.  Use a screwdriver to adjust 
the two rotary switches on the back of the detector.   
(See Figure 3.)  Set the left rotary switch (0 through 12) for the 10s 
and 100s digit and the right rotary switch for the 0 through 9 digit. 

3.  Attach the detector to the base by rotating the detector clockwise 

until it snaps into the locked position. 

4.  If required by the AHJ or local codes, affix the supplied CO 

Warning Label (P/N 3303928) in proximity to the detector. 

Figure 3: Setting detector address (address 52 shown) 

 

 

 

 

 
 
(1) Insert a screwdriver here to set the address 

Testing 

Before testing, notify the proper authorities that the fire alarm system is 
undergoing maintenance and will be temporarily out of service. 

Test each sensor in the detector.  

Note: 

If the CO sensor is programmed as an alarm point, it must 

comply with the requirements of NFPA 720. 

To perform an initial installation test: 

1. 

Visually inspect each detector and verify that it is installed in the 
correct location.  Make sure that factors not apparent on the plans 
do not adversely affect the detector. 

2. 

Remove the detector from its base and verify that the proper 
detector address, trouble signals, and messages are reported. 

3. 

If wired for Class A operation, verify that the detector continues to 
operate first with SLC_IN disconnected, and then with SLC_OUT 
disconnected. (Refer to the installation sheet for the base.) 

4. 

Place a momentary ground fault on the SLC circuit and verify 
operation of the ground fault detection circuitry. 

5. 

Perform a sensor function test, as described below. 

To perform CO sensor function tests: 

1.  Use the fire alarm control panel to put the detector into accelerated 

response mode.  (Refer to the panel technical reference manual 
for instructions.) 

2.  Activate the CO sensor using SDI LLC model Solo C6 CO aerosol 

spray without covering the head, or using the Testifire detector 
tester per the 

manufacturer’s instructions. 

To perform smoke sensor function tests: 

1.  If desired, use the fire alarm control panel to put the detector or 

zone into a service group for testing. (Refer to the panel technical 
reference manual for instructions.) 

2.  Activate the smoke sensor using No Climb Products model Smoke 

Centurion/M8, FireTech Smoke or Smoke Sabre smoke aerosol 
spray, a smoke generator, or the Testifire detector tester per the 
manufacturer’s instructions. 

Maintenance 

To ensure proper operation, plan maintenance (regular or selected) of 
the detector in accordance with the AHJ and all applicable governing 
laws, codes, or standards. Refer to NFPA 72 

National Fire Alarm and 

Signaling Code.

 NFPA 720 

Standard for the Installation of Carbon 

Monoxide (CO) Detection and Warning Equipment

Refer to application bulletin P/N 3102403-EN for additional information 
and cleaning instructions. 

CO sensor.

 The CO sensor has a 10 years life from the date of 

manufacture or when the control panel indicates a sensor end-of-life 
condition, whichever comes first. 

0

2

3

4

5

6

8

9

0

1

2

3

4

5 6 7 8

9

0

1

11

1

1

2

TENS

ONES

(1)

firealarmresources.com

Reviews: