P/N 3102530-

EN • REV 001 • ISS 16OCT18 

Specifications 

 

Operating voltage 

15.20 to 19.95 VDC 

Current 
 

Normal operating 

 

Alarm  

 
51 µA 
68 µA 

Vibration level 

10 to 35 Hz, with an amplitude of 
0.01 in. 

Wall mount distance from 
ceiling 

12 in. (305 mm) max. 

Compatible bases 
 

Standard 

 

Relay 

 

Isolator 

 

Audible 

 
KI-SB, KI-SB4 
KI-RB, KI-RB4 
KI-IB, KI-IB4 
KI-ABDT [1], KI-ABLT [1] 
KI-ABST [1] 

Compatible detector testers  

Testifire 2000 

Operating environment 
 

Temperature 

 

Relative humidity 

 
32 to 120°F (0 to 49°C) 
0 to 90% noncondensing 

Storage temperature 

−4 to 140°F (−20 to 60°C) 

Environmental compensation 

Automatic 

[1] Required for those installations that must provide separate CO 
(TC4) and fire (TC3) patterns from the sounder base. Refer to  
FX-T3T4 installation sheet p/n 3102359-EN. 

Regulatory information 

 

UL smoke 
sensitivity range 

0.53 to 3.94%/ft. (1.7  to  12.35 %/m) obscuration 

UL CO alarm level 
 
 
 
UL CO False 
alarm level 

70 ppm 60 to 240 minutes [1] 
150 ppm 10 to 50 minutes [1] 
400 ppm 4 to 15 minutes [1] 
 
30 ppm 30 days[1] 
70 ppm 60 minutes[1] 

North American 
standards 

UL 268, UL 2075 

Note: This detector has been evaluated to the CO 
alarm sensitivity limits of UL 2034. 

FCC compliance 

This device complies with part 15 of the FCC 
Rules. Operation is subject to the following two 
conditions: (1) This device may not cause harmful 
interference, and (2) this device must accept any 
interference received, including interference that 
may cause undesired operation. 

[1] Sensitivity per UL 2034 

Contact information 

For contact information, see www.kiddelifesafety.com. 