background image

 

P/N 3102678-EN • REV 001 • ISS 02DEC20 

 

3 / 4 

CO detectors are not a substitute for life safety. Though these 
detectors will warn against increasing CO levels, we do not warrant or 
imply in any way that they will protect lives from CO poisoning. They 
should only be considered as an integral part of a comprehensive 
safety program. 

Detector locations 

Selecting a suitable location is critical to the operation of CO detectors. 
Figure 2 shows appropriate detector locations. 

Verify the detector is installed in accordance with all applicable 
governing laws, codes, or standards. For combination detectors, follow 
the spacing requirements for each sensor. Refer to the control panel’s 
application bulletin for the sensor spacing requirements. 

The recommended CO detector locations are: 

• 

Outside each separate sleeping area in the immediate vicinity of 
the bedrooms (including areas such as hotel rooms and dorm 
rooms) 

• 

On every occupiable level of a dwelling unit, including basements, 
but excluding attics and crawl spaces 

• 

Centrally located on every habitable level of the building and in 
every HVAC zone based on an engineering evaluation considering 
potential sources and migration of carbon monoxide 

• 

On the ceiling in the same room as permanently installed fuel-
burning appliances 

• 

In any area required by local building codes, legislation, or the AHJ 

• 

In a suitable environment per the detector specifications (see 
“Specifications” on page 4 for details) 

• 

On a firm, permanent surface 

Do not install the CO detector: 

• 

Within 5 ft. (1.5 m) of any cooking appliance 

• 

Within 10 ft. (3 m) of a fuel-burning appliance 

• 

Near air conditioners, heating registers, or any other ventilation 
source that may interfere with CO gas entering the detector 

• 

Where furniture or draperies may obstruct the airflow 

• 

In a recessed area 

Figure 2: Recommended CO detector locations 

 

  Recommended CO detector location 

 

Testing 

Before testing, notify the proper authorities that the fire alarm system is 
undergoing maintenance and will be temporarily out of service. 

Test each sensor in the detector.  

Caution: 

Heat damage. Excessive heat may damage the detector 

outer cover. Do not apply excessive heat when using a hair dryer. 
When using a Testifire detector tester, you must install a SIGA2 
Testifire Adapter Assembly. 

Make sure the SIGA2 Testifire Adapter Assembly (model 
SIGA2-TSTSPACER) is installed in the Testifire detector tester before 
testing. Refer to the 

SIGA2 Testifire Adapter Assembly Installation 

Sheet 

(P/N 3101942-ML) for further details. 

Note: 

If the CO sensor is programmed as an alarm point, it must 

comply with the requirements of NFPA 720. 

To perform an initial installation test: 

1. Visually 

inspect 

each 

detector and verify that it is installed in the 

correct location. Make sure that factors not apparent on the plans 
do not adversely affect the detector. 

2.  Remove the detector from its base and verify that the proper 

detector address, trouble signals, and messages are reported. 

3.  If wired for Class A operation, verify that the detector continues to 

operate first with SLC_IN disconnected, and then with SLC_OUT 
disconnected. (Refer to the installation sheet for the base.) 

4.  Place a momentary ground fault on the SLC circuit to verify 

operation of ground fault detection circuitry. 

5.  Run a system detector sensitivity report on all detectors and verify 

that readings fall within acceptable limits. 

6.  Perform a sensor function test, as described below. 

To perform CO sensor function tests: 

1.  Use the fire alarm control panel to put the detector into accelerated 

response mode. (Refer to the panel technical reference manual for 
instructions.) 

2.  Activate the CO sensor using SDI LLC model Solo C6 CO aerosol 

spray without covering the head, or using the Testifire detector 
tester per the manufacturer’s instructions. 

To perform non-CO sensor function tests: 

1.  If desired, use the fire alarm control panel to put the detector or 

zone into a service group for testing. (Refer to the panel technical 
reference manual for instructions.) 

2.  Activate the smoke sensor using No Climb Products model Smoke 

Centurion/M8, FireTech Smoke or Smoke Sabre smoke aerosol 
spray, a smoke generator, or the Testifire detector tester per the 
manufacturer’s instructions. 

3.  Activate the heat sensor using a hair dryer (maintaining a distance 

of three inches) or using a Testifire detector tester per the 
manufacturer’s instructions. 

Maintenance 

To ensure proper operation, plan maintenance (regular or selected) of 
the detector in accordance with the AHJ and all applicable governing 
laws, codes, or standards. Refer to NFPA 72 

National Fire Alarm and 

Signaling Code.

 NFPA 720 

Standard for the Installation of Carbon 

Monoxide(CO) Detection and Warning Equipment

Refer to application bulletin P/N 3102650-EN for additional information 
and cleaning instructions. 

CO sensor.

 The CO sensor has a 10 years life from the date of 

manufacture or when the control panel indicates a sensor end-of-life 
condition, whichever comes first. 

firealarmresources.com

Reviews: