background image

 

4 / 4 

 

P/N 3102678-EN • REV 001 • ISS 02DEC20 

Specifications 

 
Operating voltage 

15.20 to 19.95 VDC 

Current 
 Normal 

operating 

 Alarm 

 
43 uA 
70 uA 

Actual alarm point 

129 to 141°F (53.9 to 60.6°C) 

Vibration level 

10 to 35 Hz, with an amplitude of 
0.01 in. 

Air velocity [1] 

0 to 4,000 ft./min (0 to 20.32 m/s) 

Rate-of-rise 15°F/min 

(8°C/min) 

Wall mount distance from 
ceiling  

12 in. (305 mm) max. 

Maximum spacing [2] 
for Heat Detectors 

50 ft. (15.2 m) centers 

Compatible bases 
 Standard 
 Relay 
 Isolator 
 Audible 

 
KI-SB, KI-SB4 
KI-RB, KI-RB4 
KI-IB, KI-IB4 
KI-ABDT, KI-ABLT 

Compatible detector testers [3]  Testifire 2000 

Operating environment 
 Temperature 
 Relative 

humidity 

 
32 to 100°F (0 to 38°C) 
0 to 90% noncondensing 

Storage temperature 

4 to 140°F (

20 to 60°C) 

Environmental compensation 

Automatic 

[1] For duct installation, use a KI-DMP duct detector mounting plate 
and install per P/N 3102482-EN.  

[2] When replacing KI-HFD and KI-HRD detectors with the KIR-
OSHCD, ensure that the spacing is 50 ft. (15.2 m) or less. 
[3] Requires the SIGA2-TSTSPACER Testifire adapter assembly. 

Regulatory information 

 
UL smoke 
sensitivity range 

0.5 to 4.36 %/ft. (1.63 to 13.62 %/m) obscuration 

UL fixed-
temperature alarm 
rating 

135°F (57.2°C) 

UL CO alarm level 
 
 
 
UL CO False 
alarm level 

70 ppm 60 to 240 minutes [1] 
150 ppm 10 to 50 minutes [1] 
400 ppm 4 to 15 minutes [1] 
 
30 ppm 30 days[1] 
70 ppm 60 minutes[1] 

North American 
standards 

UL 268-7, UL 521, UL 2075 
Note: This detector has been evaluated to the CO 
alarm sensitivity limits of UL 2034. 

FCC compliance 

This device complies with part 15 of the FCC 
Rules. Operation is subject to the following two 
conditions: (1) This device may not cause harmful 
interference, and (2) this device must accept any 
interference received, including interference that 
may cause undesired operation. 

[1] Sensitivity per UL 2034 
 

Contact information 

For contact information, see www.kidde-esfire.com. 

 

 

 

firealarmresources.com

Reviews: