The closed door may prevent an alarm not located in that room
from waking the sleeper.

• Smoke, heat, and combustion products rise to the ceiling and

spread horizontally.  Mounting the smoke alarm on the ceiling in
the center of the room places it closest to all points in the room.
Ceiling mounting is preferred in ordinary residential 
construction. 

• For mobile home installation, select locations carefully to avoid

thermal barriers that may form at the ceiling.  For more details, see
MOBILE HOME INSTALLATION below.

• When mounting an alarm on the ceiling, locate it at a minimum of

4” (10 cm) from the side wall (see figure 1).

• When mounting the alarm on the wall, use an inside wall with

the top edge of the alarm at a minimum of 4” (10 cm) and a
maximum of 12” (30.5 cm) below the ceiling (see figure 1).

• Put smoke alarms at both ends of a bedroom hallway or large

room if the hallway or room is more than 30 feet (9.1 m) long.

BEDROOM

BEDROOM

KITCHEN

LIVING ROOM

BEDROOM

BEDROOM

BEDROOM

BASEMENT

KITCHEN

HALL BEDROOM

LIVING
ROOM

SINGLE FLOOR PLAN

MULTIPLE

FLOOR PLAN

NOT

IN THIS

(10 cm)

4"

MINIMUM

(10 cm)

4"

CEILING

DEAD AIR

SPACE

SIDE

WALL

MINIMUM

(30.5 cm)

12"

MAXIMUM

BEST

HERE

NEVER

HERE

ACCEPTABLE

HERE

FIGURE 2

FIGURE 3

FIGURE 1

(0.9 m)

3'

(102 mm)

4"

NOT

IN THIS

AREA

ANYWHERE

IN THIS AREA

(0.9 m)

3'

(0.9 m)

3'

(102 mm)

4"

NOT

IN THIS

AREA

ANYWHERE

IN THIS

AREA

0910-7225-00(21008311A)_EN.qxd:_  2011.3.22  10:05 AM  Pag

Summary of Contents for i9010

Page 1: ...important part of your family s home safety plan You can trust this prod uct to provide the highest quality safety protection We know you expect nothing less when the lives of your family are at stake...

Page 2: ...S 4 OPERATION AND TESTING 5 NUISANCE ALARMS 6 MAINTENANCE 7 LIMITATIONS OF SMOKE ALARMS 8 GOOD SAFETY HABITS 9 NRC INFORMATION 10 NFPA PROTECTION STANDARD 72 11 CALIFORNIA STATE FIRE MARSHAL REQUIRED...

Page 3: ...inimum of 4 10 cm from the side wall see figure 1 When mounting the alarm on the wall use an inside wall with the top edge of the alarm at a minimum of 4 10 cm and a maximum of 12 30 5 cm below the ce...

Page 4: ...g an alarm mounted on the ceiling In such units install the smoke alarm on an inside wall with the top edge of the alarm at a minimum of 4 10 cm and a maximum of 12 30 5 cm below the ceiling see figur...

Page 5: ...nuisance alarms Smoke alarms are not to be used with detector guards unless the combination alarm and guard has been evaluated and found suitable for that purpose 3 INSTALLATION INSTRUCTIONS CAUTION...

Page 6: ...1 To activate the alarm install the alarm on the mounting bracket figure 6 and rotate the alarm clockwise as indicated on the alarm cover until the alarm ratchets into place the ratcheting function al...

Page 7: ...rm will automatically reset after approximately 8 minutes and sound the alarm if particles of combustion are still present The SMART HUSHTM feature can be used repeatedly until the air has been cleare...

Page 8: ...The alarm memory is reset when the test button is released TESTING Test by pushing the test button on the cover and holding it down for a minimum of 5 seconds or until the alarm sounds This will soun...

Page 9: ...et by rotating in the direction of the arrows on the cover see ACTIVAT ING ALARM in Section 3 INSTALLATION INSTRUCTIONS This alarm has a low battery monitor circuit which will cause the alarm to chirp...

Page 10: ...operation the alarm should be replaced 7 LIMITATIONS OF SMOKE ALARMS WARNING PLEASE READ CAREFULLY AND THOROUGHLY NFPA 72 states Life safety from fire in residential occupancies is based primarily on...

Page 11: ...e up a sound sleeper The use of alcohol or drugs may also impair one s ability to hear the smoke alarm For maximum protection a smoke alarm should be installed in each sleeping area on every level of...

Page 12: ...Alert small children in the home Leave immediately by your escape plan Every second counts so don t waste time getting dressed or picking up valuables In leaving don t open any inside door without fi...

Page 13: ...ng rooms 3 On each level of the dwelling unit includ ing basements Exception In existing one and two family dwelling units approved smoke alarms powered by batteries are permitted Smoke Detection Are...

Page 14: ...rooms dining rooms bedrooms kitchens hallways attics furnace rooms closets utility and storage rooms basements and attached garages The NFPA suggests that alarms installed within 20 6 1m of cook ing...

Page 15: ...F ITS PARENT OR SUBSIDIARY CORPORATIONS ARISING FROM THE SALE OF THIS SMOKE ALARM OR UNDER THE TERMS OF THIS LIMITED WARRANTY SHALL NOT IN ANY CASE EXCEED THE COST OF REPLACEMENT OF SMOKE ALARM AND IN...

Reviews: