TM206
27 of 35
Issue 1.0
To save the settings, slide the
WRITE ENABLE
switch gently to the right.
The extinguishing output levels will now be set and any significant variation detected in the monitoring
levels will be announced as an
EXTING. O/P
fault.
15 Panel operation – Access levels 1 and 2
15.1 Normal
condition
Under normal conditions and in Manual & Auto mode, the ECU will have only the green
Power On
LED
lit. With the
ENABLE CONTROL
keyswitch off the LCD on the ECU will show:
In
Manual only
mode the ECU will have an additional, Manual only yellow LED lit and the LCD will show:
The ECU has 3 access levels. Access level 1 is available at all times and allows operation of SILENCE
BUZZER and the Lamp test function (hold down EXIT button for more than 2 seconds). Access level 2 is
enabled after operation of the front panel mounted
ENABLE CONTROL
keyswitch. Access level 3 allows
configuration options to be set on the ECU following operation of the
WRITE ENABLE
while in access
level 2 (
ENABLE CONTROLS
keyswitch operated).
15.2 Access level 2
When the
ENABLE CONTROLS
keyswitch is operated the LCD on the ECU will show:
Press the
ENTER
button to view the following menu options.
15.2.1 Disable Extinguishing release outputs.
To disable both of the Extinguishing release outputs, press the
UP
button on the module while at access
level 2.
The display will show:
Press the
ENTER
button to select this function. The display will show:
The yellow disabled LED on the ECU will be lit.
Turn the
ENABLE CONTROL
keyswitch off to leave the disablement active. To re-enable the
extinguishing outputs repeat the procedure above.
15.2.2 Disable Manual release
To disable all Manual release inputs (front panel mounted and remotely connected); press the
UP
button
on the module while at access level 2 until the module displays: