TM206
22 of 35
Issue 1.0
14.5 Extinguishing release time
The time that the Extinguishing output is active for can be set between 60 and 300 seconds. The factory
default time for this is 60 seconds. It is also possible to disable this timer such that the Extinguishing
outputs remain active until the module is reset. See Release timer menu option section 14.11.
To change the Extinguishing release time, switch on the
ENABLE CONTROL
keyswitch and slide the
WRITE ENABLE
switch on the module to be configured gently to the left. Press the
ENTER
button on
the ECU then press the
UP
button until the display shows:
Press the
ENTER
button and the display will show:
To change the time, press the
UP
or
DOWN
buttons until the required time is displayed
To save the settings, slide the
WRITE ENABLE
switch gently to the right.
The Extinguishing release time will now be set to the chosen value.
14.6 2
nd
stage alarm
The second stage alarm output can be configured to be steady or pulsing at about 1 second on, 1
second off to suit the desired application. The factory default for the second stage alarm is pulsing.
To change the operation of the second stage sounders, switch on the
ENABLE CONTROLS
keyswitch
and slide the
WRITE ENABLE
switch on the module to be configured gently to the left. Press the
ENTER
button on the ECU then press the
UP
button until the display shows:
Press the
ENTER
button and the display will show:
To change to steady second stage alarms, press the
ENTER
button.
To save the settings, slide the
WRITE ENABLE
switch gently to the right.
The second stage alarm output will operate in steady mode when the module is activated.
14.7 Released
indication
It is possible to select whether the released indication on a module is operated at the same time as the
extinguishing release output operates or by operation of a pressure switch connected to the released,
pressure switch input.
The factory default setting is for the released indication to be operated by operation of a pressure switch
connected to the released, pressure switch input.
To change the operation of the released indication, switch on the
ENABLE CONTROLS
keyswitch and
slide the
WRITE ENABLE
switch on the module to be configured gently to the left. Press the
ENTER
button on the ECU then press the
UP
button until the display shows: