• Put smoke alarms at both ends of a bedroom hallway or large room if the hallway
or room is more than 9.1 m (30 feet) long.
• Install Smoke Alarms on sloped, peaked or cathedral ceilings at or within 0.9 m (3
ft) of the highest point (measured horizontally). Smoke alarms in rooms with ceil-
ing slopes greater than .3 m in 2.4 m (1 foot in 8 feet) horizontally shall be located
on the high side of the room. A row of detectors shall be spaced and located
within 0.9 m (3 ft) of the peak of the ceiling measured horizontally (see Figure 3).
Smoke Alarms for Minimum Protection
Smoke Alarms for Additional Protection
Heat Alarms for Additional Protection
FIGURE 2
FIGURE 3
FIGURE 1