C-3
August 1999
76-100016-001
Intelligent Suppression Control/Fire Alarm System
PEGAsys
C-6
AGENT RELEASE APPLICATIONS
C-6.1
CCM Release Output Wiring
The
PEGAsys
system provides one output on the CCM (MP01,
Terminal TB4(A)), is fully supervised and can is defaulted as a
release output. Refer to Appendix I, Drawing No. 06-235443-
001, and to the PCS program user’s guide for details on the
configuration of this output.
An example of the CCM releasing circuit wiring is shown in Fig-
ure C-3. For wiring details refer to the CCM wiring diagram,
Drawing No. 06-235443-001 (Appendix I).
Figure C-3. CCM Release Output, Wiring Basics
C-6.2
Release Module Output Wiring
The agent release modules which the
PEGAsys
system uses to
provide the release function offer one release output capable of
powering two solenoids simultaneously. Refer to Appendix I,
Drawing No. 06-235443-005, and to the PCS program user’s
guide for details on configuration of the release outputs along
with all other system parameters.
All wiring from the agent release module to the release device is
fully supervised, including the actual device in the circuit. Ex-
amples of the releasing circuit wiring is provided in figure C-4.
For all wiring detail refer to the Release Module wiring diagram,
drawing number 06-235443-005 (in Appendix I) for specific wir-
ing details. For a list of approved devices, refer to Table 3-2 in this
manual.
Figure C-4. Release Module, Wiring Basics
C-7
PRE-ACTION SPRINKLER APPLICATIONS
The
PEGAsys
system can be used to activate and supervise pre-
action sprinkler and deluge sprinkler systems for protection of fa-
cilities. The CCM output (MP1) and agent release output modules
(AR1 - AR8) can be programmed for use with most popular sprin-
kler solenoids.
For sprinkler applications the addressable input module P/N 70-
407008-00x can be used to monitor and supervise any of the fol-
lowing sprinkler type inputs as required for each particular
application. Inputs could be air pressure, waterflow, water level
(tank), pump running, etc. Refer to Chapter 2 for details on pro-
gramming the addressable input device for various reporting
styles.